Do not install wooden beams or any other
flammable material on the hood above the appliance:
danger of fire.
The front fairing above the door is one of the hottest parts of
the appliance, so be very careful when making the front
cover of the hood and any cover you are going to make
(paints, stucco, adhesives, porcelain stoneware slabs,
etc...); check the technical data sheet of the aforementioned
materials for their suitability for high temperatures and also
pay attention to thermal expansions that could generate
cracks or breaks in them (the manufacturer declines any
responsibility for damage to the coating).
To avoid these possible inconveniences, we strongly
recommend making the coating using calcium silicate
panels or at least to internally insulate at least the front
hood with a semi-rigid 3 cm rock wool panel with
aluminum foil (eg Rockwool Firerock), rock wool in
contact with the plasterboard, aluminum foil facing the
chimney, leaving in this case a minimum distance from
the appliance of at least 20 mm.
Fireproof
plasterboard
It is forbidden to use flammable
materials (such as wood) for
the
construction
of
the
supporting structure of the
cladding (which must be self-
supporting and not in contact
with the appliance), instead use
components in aluminum or
galvanized steel.
If your appliance is equipped
with air slots on the front fairing,
it is forbidden to position the
uprights of the frame for the
plasterboard on the same slots
(as the cooling air passage is blocked): position the profile at a greater
height than the slots themselves.
L'ARTISTICO SRL | EN
All manuals and user guides at all-guides.com
INSULATING 3 cm
28
AIR INTAKES IN THE COVERING
To avoid overheating of the appliance it is mandatory to carry out
inside the structure that covers the chimney, a recirculation of air with
one or more openings in the lower and upper part of the cladding.
The measures to be respected are the following:
- cold air inlet taken from the environment on the lower part of
minimum total area 450 cm²
- hot air outlet of natural convection on the upper part of
minimum total area 450 cm² - 500 cm² .
IMPORTANT: this convective air outlet section is used
to vent the heat from the cladding, it does not include
the ducted air outlet pipes which must therefore be
added and calculated separately.
All openings made to create good air circulation must, through
grilles or suitable protective parts, prevent access to dangerous
parts, while ensuring the minimum required air passage.
INSPECTION DOOR
Each pellet fireplace model requires a mandatory inspection door for
ordinary and extraordinary maintenance of the appliance of at least
50x140 cm.
CONNECTING PIPES HOT AIR FANS
When the fans are present, they must be connected to air distribution
nozzles.
It is forbidden, subject to warranty termination, not
to connect the air hoses as shown in the following
diagram.
It is strictly forbidden to move the electrical
components and the smoke extractor at a later date, as
long as the guarantee is declined. It is an operation that
must be done exclusively at the factory or an authorized
service center.
According to the models respect the following indications.