9. Test run
9.3. Self-check
Refer to the installation manual that comes with each remote controller for details.
RF thermostat is not established.
[Output pattern A] Errors detected by indoor unit
Wired remote controller
IR wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp flashes
(Number of times)
1
P1
2
P2, P9
3
E6, E7
4
P4
5
P5
6
P6
7
EE
8
P8
9
E4
10
11
12
Fb
No sound
[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wired remote controller
IR wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp flashes
(Number of times)
1
E9
2
UP
3
U3, U4
4
UF
5
U2
6
U1, Ud
7
U5
8
U8
9
U6
10
U7
11
U9, UH
12
13
14
Others
*1 If the beeper does not sound again after the initial two beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp does
not come on, there are no error records.
*2 If the beeper sounds three times continuously beep, beep, beep (0.4 + 0.4 + 0.4 sec.) after the initial two beeps to confirm the self-check start signal was
received, the specified refrigerant address is incorrect.
On IR wireless remote controller
The continuous buzzer sounds from receiving section of indoor unit.
Blink of operation lamp
On wired remote controller
Check code displayed on the LCD.
If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.
Wired remote controller
PLEASE WAIT
PLEASE WAIT Error code
Display messages do not appear
even when operation switch is
turned ON (operation lamp does
not light up).
On the IR wireless remote controller with conditions above, following phenomena takes place.
No signals from the remote controller are accepted.
OPE lamp is blinking.
The buzzer makes a short ping sound.
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
RF thermostat
Check code
Intake sensor error
Pipe (Liquid or 2-phase pipe) sensor error
Indoor/outdoor unit communication error
Drain sensor error
Drain pump error
Freezing/Overheating safeguard operation
Communication error between indoor and outdoor units
Pipe temperature error
Remote controller signal receiving error
Indoor unit control system error (memory error, etc.)
No corresponding
RF thermostat
Check code
Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)
Compressor overcurrent interruption
Open/short of outdoor unit thermistors
Compressor overcurrent interruption (When compressor locked)
Abnormal high discharging temperature/49C worked/insufficient refrigerant
Abnormal high pressure (63H worked)/Overheating safeguard operation
Abnormal temperature of heat sink
Outdoor unit fan protection stop
Compressor overcurrent interruption/Abnormal of power module
Abnormality of super heat due to low discharge temperature
Abnormality such as overvoltage or voltage shortage and abnormal
synchronous signal to main circuit/Current sensor error
Other errors (Refer to the technical manual for the outdoor unit.)
Symptom
LED 1, 2 (PCB in outdoor unit)
For about 2 minutes
After LED 1, 2 are lighted, LED 2 is turned off,
following power-on
then only LED 1 is lighted. (Correct operation)
Only LED 1 is lighted. LED 1, 2 blink.
After about 2 minutes
has expired following
power-on
Only LED 1 is lighted. LED 1, 2 blinks twice,
LED 2 blinks once.
Symptom
Symptom
For about 2 minutes after power-on, operation of the
remote controller is not possible due to system start-up.
(Correct operation)
Connector for the outdoor units protection device is not
connected.
Reverse or open phase wiring for the outdoor units power
terminal block (L1, L2, L3)
Incorrect wiring between indoor and outdoor units
(incorrect polarity of S1, S2, S3)
Remote controller wire short
Remark
Remark
For details, check the LED
display of the outdoor controller
board.
Cause