NEXSYS Series Rackmount PDU User Manual
Model
EMI Filter, Differential
Mode
50Ω Load
EMI Filter, Common
Mode
50Ω Load
Overvoltage
Threshold
Undervoltage
Threshold
Physical
Model
Dimensions
(Width x Height x Depth)
Product Weight
Shipping Weight
Warranty
Model
Series Surge Module
PDX-915R-SP
40dB@100kHz
50dB@3MHz
18dB@100kHz
50dB@3MHz
Upper Limit Cutoff: 135V RMS
Upper Limit Restore: 126V RMS
Lower Limit Cutoff: 100V RMS
Lower Limit Restore: 105V RMS
PDX-915R-SP
19" (483mm) x 1.735" (44mm) x 8.75" (222mm)
8.6 lb. (3.9 kg)
11.47 lb. (5.2 kg)
PDX-915R-SP and PDX-920R-SP
Twelve Years Limited
For warranty information, refer to
www.legrandav.com/policies/warranty_information.
23
©2023 |
Legrand AV,
Inc. All rights reserved.
Specifications
PDX-920R-SP
50dB@100kHz
50dB@30MHz
30dB@100kHz
50dB@30MHz
PDX-920R-SP
12.35 lb. (5.6 kg)