NEXSYS Series Rackmount PDU User Manual
Hardware Features
Model
Surge Protection
Peak Impulse
Current
(8/20µS Waveform)
Protection Mode
Response Time
Surge Energy
Dissipation
Voltage Protection
Rating
EMI/RF Suppression
Overvoltage
Threshold
Undervoltage
Threshold
45,000 Amps, one time - Maximum peak impulse current pulse as
defined between line and neutral. 19,500 Amps, two times within 5
minutes - Maximum multiple impulse current derated per spec.
Line to Neutral only; no ground contamination.
>20dB Calculated Line to Neutral - 100kHz to 1Mhz - based on nominal
Upper Limit Cutoff: 135V RMS
Upper Limit Restore: 126V RMS
Lower Limit Cutoff: 100V RMS
Lower Limit Restore: 105V RMS
©2023 |
Legrand AV,
PDX-915R and PDX-920R
Multi-Stage MOV
Less than 1 nanosecond.
705 Joules (10/100µS)
500V (L-N); Type 3 SPD
impedance.
20
Inc. All rights reserved.
Specifications