Section B – Using the Jetflush Rapid pump for power flushing
drain pipe gully leading to a foul
sewer.
1e. Connect mains water supply
hose ¾" BSP female hose
connector to the ¾" brass nipple
on the rear of the hose support
plate. Fill the tank with water to
10cm above the minimum liquid
level, and then close the water
inlet valve.
1f. Plug in the pump to a suitable 13
amp electricity supply fitted with
an RCD adapter.
2. Hose connection to the system
Connect the flow and return hoses
of the pump to the system at the
selected point. This may be either:
2a. Across the 1½" BSP unions left
once the circulating pump has
been removed. The circulating
pump isolating valves should
be closed to isolate the flushing
pump from the system until
power flushing is commenced.
When used these are screwed
directly onto the ¾" female brass
hose adaptors of the flow and
return hoses.
2b. Across the "tails" of a
radiator (having drained and
Jetflush Rapid V1-02-15
Jetflush Rapid Guidelines (19-02-15).indd 11
disconnected the radiator)
using appropriate ½"or ¾"
BSP adaptors to connect to
the valves. The radiator valves
should be closed to isolate
the flushing pump from the