QM5 AND QS5 HANDBOOK
Parallel connection number of slots
Number of modules in parallel
slots
SB
2
2
3
1
4
0
3
3
4
4
See ratings in
Module output ratings table below
Combined DM modules – series connected Channel 1 only.
Number of
modules
outputs
2
3
3
4
4
5
5
6
Input Parameters:
Standard
Nominal input voltage
Input voltage range
Input frequency range
Maximum input current
* Input for 800W or 1200W models.
**Output power is derated to 650W between 85-89.9Vac.
Input Connections:
3 way Terminal block: 8.25mm spacing between screw head centres. M3 screws, 0.5Nm torque, 20A/300V
MAX.
Faston: 6.3 x 0.8mm, Tin plated brass, rated 22A.
IEC Connector: 10A/250Vac.
SC
0
1
2
0
0
v1/v2/v3MC
v1/v2/v3/v4MD
v1/v2/v3/v4/v5MF
v1/v2/v3/v4/v5/v6MG
Input parameters
rd
60601-1 3
Edition
100-240Vac
200-240Vac*
144-318Vdc
239-318Vdc*
**85-264Vac
(180-264Vac)*
130-350Vdc
215-350Vdc*
47-63
dc
11Arms or 7Adc
9Arms or 7Adc*
Page 20 of 37
Name
ZC
ZD
ZF
ZT
ZV
Nomenclature
60950-1 & 62368-1
100-240Vac
200-240Vac*
144-318Vdc
239-318Vdc*
**85-264Vac
(180-264Vac)*
130-350Vdc
215-350Vdc*
47-440Hz
dc
11Arms or 7Adc
9Arms or 7Adc*
260362-07, Mar 2020