Configuration
12
Select Battery Type - REQUIRED
CAUTION: The Battery Type DIP Switch setting must match the type of
batteries you connect, or your batteries may be degraded or damaged
over an extended period of time. See "Battery Selection," for more
information.
Battery Type
AGM/Gel Cell (Sealed) Battery Up
Wet Cell (Vented) Battery
Set Battery Charge Conserver (Load Sense) Control—OPTIONAL
In order to save battery power, the unit's inverter automatically shuts off in the absence of any power demand from
connected equipment or appliances (the electrical load). When the Inverter/Charger detects a load, it automatically turns its
inverter function on. Users may choose the minimum load the Inverter/Charger will detect by adjusting the Battery Charge
Conserver Control (see diagram). Using a small tool, turn the control clockwise to lower the minimum load that will be
detected, causing the inverter to turn on for smaller loads. When the control is turned fully clockwise, the inverter will
operate even when there is no load. Turn the control counterclockwise to increase the minimum load that will be
detected, causing the inverter to stay off until the new minimum load is reached.
NOTE: The factory setting for the control is fully clockwise. However, based on the threshold load to which you'd like the inverter to respond, you should adjust the control counterclockwise to reduce
its sensitivity until the inverter is active only when connected equipment or appliances are actually in use.
Connect Remote Control—OPTIONAL
The unit features an 8-conductor telephone style jack on the front panel for use with an optional remote control module (Tripp Lite model
APSRM4, sold separately). The remote module allows the Inverter/Charger to be mounted in a compartment or cabinet out of sight, while operated
conveniently from a remote location. See instructions packed with the remote control module.
Connect Battery Temperature Sensing Cable—OPTIONAL (Contact Tripp Lite for optional temperature sensing cable
accessory.)
The battery temperature sensing function prolongs battery life by adjusting the charge float voltage level based on battery temperature.
Connect the sensor cable (the cable has an RJ style connector on one end and a sensor on the other) to the RJ style jack located on the front
panel of the Inverter/Charger labeled "RMT BATT TEMP." With user-supplied electrical or duct tape, affix the sensor to the side of the
battery below the electrolyte level. Make sure that nothing, not even tape, comes between the sensor and the side of the battery. To guard
against false readings due to ambient temperature, place the sensor between batteries, if possible, and away from sources of extreme heat
or cold. If the sensor cable is not used, the Inverter/Charger will charge according to its default value
(25º C).
Connect Automatic Generator Starter—OPTIONAL
Connect the RJ type modular jack on the front panel labeled "RMT GEN START" to separate
generator ON/OFF switching mechanism with user-supplied cable (see Pin Configuration Diagram).
Once attached, the interface will allow the Inverter/Charger to automatically switch a separate
generator on when connected battery voltage levels are low and switch it off when
battery voltage levels are high.
All manuals and user guides at all-guides.com
(continued)
9 10 11 12
Switch Position
Down (factory setting)
AGM/
Gel Cell
7
LOAD
SENSE
MAX OFF
Pin Configuration
1
2 - Common
2
3 - N.C.
3
(Normally Closed)
4
4 - N.O.
5
(Normally Open)
6