6. Programming
Take the following 3 steps for programming:
1
Mode/Enter Set
Mode/Enter Set
2
3
Mode/Enter Set
Wait 5s (the unit passes to the operating mode and
or start again with step 1 to program other parameters.
*Decrease the value: Let the display of the parameter value move to the
maximum setting value. Then the cycle starts again at the minimum setting
value.
If no button is pressed for 20s during the setting procedure, the unit
returns to the run mode.
Locking / Unlocking
The unit can be electronically locked to prevent unwanted adjustment
of the set parameters: Press (in Run mode) both setting buttons for
10s. As soon as the indication goes out the unit is locked or unlocked.
Units are delivered from the factory in the unlocked state.
With the unit in the locked state
to change parameter values.
24
the current measured value is indicated again),
Press the Mode/Enter button
several times until the respective
parameter is displayed.
Press the Set button and keep
it pressed. The current parameter
value is indicated for 5s,
then the value is increased*
(incremental by pressing briefly or
scrolling by holding pressed).
Press the Mode/Enter button
briefly (= acknowledgement).
The parameter is displayed again,
the set parameter value
becomes effective.
is indicated briefly when you try