Télécharger Imprimer la page

IFM Electronic efector500 PI76 Notice Utilisateurs page 22

Capteur de pression électronique

Publicité

Les langues disponibles

Les langues disponibles

4. Electrical connection
The unit must only be connected by an electrician.
The national and international regulations for the installation of
electrical equipment must be observed.
Voltage supply to EN50178, SELV, PELV.
Disconnect power before connecting the unit.
Wiring:
4: OUT1
2: OUT2
5. Adjustable parameters
(Menu structure: see fold out page)
Switch-on point: Upper limit value at which the output changes
its switching status.
• setting range 1 ... 100% of the value of the measuring range
• in steps of 0.5% of the value of the measuring range
• indicated in bar
Switch-off point: Lower limit value at which the output
changes its switching status.
• setting range 0.5 ... 99.5% of the value of the measuring range
• in steps of 0.5% of the value of the measuring range
• indicated in bar
rPx is always lower than SPx. The unit only accepts values which
are 0.5% lower than SPx.
Changing the switch-on point also changes the switch-off point
(the distance between SPx and rPx remains constant).
If the distance is higher than the new switch point, it is automati-
cally reduced (rPx is set to the minimum setting value).
22
1
BN
L +
2
WH
4
BK
3
BU
L
Core colours of ifm sockets:
1 = BN (brown), 2 = WH (white),
3 = BU (blue), 4 = BK (black).
Programming of complementary
outputs:
output 1: = Hno, output 2: = Hnc,
SP1 = SP2 / rP1 = rP2.

Publicité

loading