Technical data valve
Max. operating temperature: Long-term: 120 °C
Short-term: 140 °C
Material
Vlave body: corrosion-resistant red bronze
Internal parts: brass and corrosion resistant steel
Seal: EPDM
Max. pressure: 10 bar
Connection thread: ½
, ¾
"
Technical data actuator
Power supply: 230 V~, 50 ... 60 Hz
Current consumption (typical): 26 mA
Power consumption: max. 2,5 W
Switch-on current: < 1A
Initial position:
SVA-NC: normally closed
SVA-NO: normally open
Operating temperature: -25 ... 50 °C
Spring force: 90 N
Stroke: 4 mm
Protection type: IP 44 (when mounted vertically to the top)
Protection class: II
Actuation time: ca. 3 min
Pollution degree: 2
Connection cable: 2 x 0,5 mm²; 100 cm
12
All manuals and user guides at all-guides.com
, 1
,1¼
"
"
"
actuating variable
to
to
actuating variable
mass flow rate m [kg/h]
calculation example 1
to
actuating variable
to
actuating variable
mass flow rate m [kg/h]
calculation example 1