Installation and operating instructions
NOTE
ATTENTION
Compact wall-mounted units KWL EC 200/300 W R/L
2.8
Functional layout
Pos.
Name
T1
Outside air sensor
T2
Supply air sensor
T3
Extracted air sensor
T4
Outgoing air sensor
T6
Duct sensor Type KWL-LTK (accessories)
T7
Frost-protection sensor Type KWL-LTK (accessories) for WW-register return
T11-T18
Humidity/temperature sensor: KWL-FTF (accessories)
1
Temp-resistant or non-flammable duct (e.g. spiral duct)
2
Iso-Pipe duct Ø 125
Connector with seal for unit connection to ductwork: RVBD 125
3
4
Electric pre-heater internal: KWL EVH 200/300W
5
Electric auxiliary heater Type HER-R 1.2/125 + KWL EM + KWL LTK
Hot water auxiliary heater Type: WHR 125
and hydraulic unit
Alternative
2.9
Initial start-up and adjustment
Useful hint for adjustment!
The adjustment by means of pressure measurement is explained in the Helios practical workshops, and
this is the easiest way to adjust a KWL EC 200/300 W R/L. In this respect, a pressure measuring
connector must be mounted to each connecting socket/ventilation pipe (approx. 20 cm past the unit
connection), and the pressure hoses must be readily accessible.
To balance the whole system, supply and extract openings should be provided with adjustable elements
or valves (accessories). During extraction of polluted extract air, a filter (accessories) is to be
connected. The installation of kitchen hoods to the system (cause: dirt, fire danger, hygiene) is not
permitted. To ensure air circulation within the room sufficient overflow openings (door gap, door grilles)
are to be planned.
All fire regulations must be observed!
Detailed information on the adjustment of KWL wall-mounted units can be found in the
TIP!
Installation and Operating Instructions "KWL easyControls Initial start-up"; No. 82 237!
When using a heating coil, the duct system must be provided with temperature-resistant and non-
flammable ducts (e.g. spiral duct) 1m before and after the heating coil.
Fig. KWL EC 200/300 W Right
+ WHSH 1100 24V (0-10V)
+ KWL EM
+ 2x KWL LTK (T6+T7)
9
GB
Item No.
-----
-----
-----
-----
09644
09644
04273
-----
-----
09640
04224
09433
04269
09644
09480
08819
04269
09644