Télécharger Imprimer la page

Mitsubishi Electric CITY MULTI Smart ME Controller Manuel D'installation page 16

Publicité

Les langues disponibles

Les langues disponibles

2
Service Menu
[HOME screen]
A password is required to access the Menu
.
screen
• The initial Service password is "9999." The initial User password is "0000." Change the password
as necessary to prevent unauthorized access.
• Make sure the password is available to the maintenance and other necessary personnel.
• The password can be changed to any four-digit number. On the [Login page], enter the old
password, touch the [Change] button, and then enter a new password.
Service menu items
Item
Detail
Description
(1) Setup (a) Group
Make the group setting for the
setting
indoor units, and an AHC
(b) Interlocked
Enters the interlock settings
LOSSNAY
between indoor and LOSSNAY
units
(c) Search
Use to search and display the
connection
units that are connected to a
information
specified unit.
(d) Cool/Heat
Use to show or hide the
display
operation mode signs (Cool/
Heat) on the HOME screen
while the units are operated in
the Auto mode or the Setback
mode.
(e) Override
Use to enable or disable the
control
Override function and to set the
override time when the function
is enabled.
* Use to enable or disable the
(f)
Temperature
Use to offset the reading on the
sensor offset
built-in temperature sensor. *1
(g) Humidity
Use to offset the reading on the
sensor offset
built-in humidity sensor.
(h) Auto mode
Use to select the number of set
Single/Dual
points (single/dual) to be used
in the Auto mode.*2
[MENU(User) screen]
Service
screen or some settings under the Menu
(
)
function that restores the
original set temperature after
the preset override time has
elapsed (when the set
temperature was changed
while the units were operated
in the Setback mode).
– 16 –
[MENU(Service) screen]
Setting
Default
Refer to section 1
"Initial Settings" (2)
"Setup screen".
Select between Show/
Auto: Show
Hide.
Setback: Show
• Select between
Override: Enable
Enable and Disable.
Override time: 2:00
• Set the override time in
5-minute increments
(max. 9 hours and 50
minutes ).
Set the offset value.
Offset: 0ºF (0.0ºC)
(-5ºC~+5ºC)
(-10ºF~+10ºF)
Set the offset value.
Offset: 0%
(-10%~+10%)
Select between single
and dual.
(Varies depending on the
* Not available if the air
connected indoor unit
conditioning units do
model.)
not feature the Auto
function.
User
(
)