Installation instructions, only for experts
5.7. Installing humidity temperature sensor FTS2 (optional)
1. Guide the wires for the sensor through the cable bushing
voltage connection area
2. Connect the wires for the temperature sensor to the terminals labelled "F2"
in terminal strip
a. Connect the black wire to the right terminal.
b. Connect the brown wire to the left terminal.
3. Connect the wires for the humidity sensor to the terminals labelled "+ S -"
in terminal strip
c. Connect the green wire to terminal "+".
d. Connect the orange wire to terminal "S".
e. Connect the red wire to terminal "-".
5.8. Connecting the safety shut-off
EN 60335-2-53 states that sauna control units with remote control may only be
used for operating and regulating a sauna heater which has satisfied the combus-
tion test described in paragraph 19.101. Alternatively, a suitable safety shut-off
device can be installed in or above the heater. This shuts the sauna heater off
when objects, e.g. a towel, are placed on the sauna heater.
To install the safety shut-off device, perform the following steps:
1. Install the safety shut-off device in accordance with the operating instruc-
tions for the device.
2. Guide the wires for the safety shut-off device through the cable bushing
into the low-voltage connection area
3. Connect the wires to the terminals labelled "OSG" in terminal strip
If a safety shut-off is not installed, a jumper must be fitted at the terminals
labelled "OSG".
.
1
.
2
.
2
.
1
p. 19/38