G
®
THERMASGARD
Calibratable tube contact temperature measuring transducer THERMASGARD
sensor, continuous output, rugged housing made from stainless steel V4A, with cable gland or M12 connector according to DIN EN 61076-2-101.
The surface-contact sensor is used for temperature detection on lines, pipes (e.g. cold and hot water) or on heating sections for heating system
control. The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.
TECHNICAL DATA
Power supply:
Working resistance:
Load resistance:
Power consumption:
Insulating resistance:
Sensor:
Measuring ranges:
Deviation, temperature:
Output:
Connection type:
Cable connection:
Housing:
Housing dimensions:
Sensor cable:
Sensor protection:
Electrical connection:
Process connection:
Ambient temperature:
Permitted humidity:
Protection class:
Protection type housing:
Protection type sensor:
Standards:
THERMASGARD
®
ALTM 2 - VA Surface contact ⁄ tube contact temperature measuring transducers, ID
®
THERMASGARD
ALTM 2 - VAQ Surface contact ⁄ tube contact temperature measuring transducers, ID
Type ⁄ WG02I
ALTM 2 - VA
A LT M 2 - I VA
A LT M 2 - U VA
ALTM 2 - VAQ
A LT M 2 - I VA Q
A LT M 2 - U VA Q
Housing variant "Q":
Extra charge:
ACCESSORIES
ALTM2 - VA
24 V AC ⁄ DC (± 10 %) for U variant
15...36 V DC for I variant, depending on working resistance, residual ripple stabilised ± 0.3 V
R
(ohm) = (U
-14 V) ⁄ 0.02 A for I variant, see working resistance diagram
a
b
R
> 5 kOhm for U variant
L
< 1.0 VA ⁄ 24 V DC; < 2.2 VA ⁄ 24 V AC
≥ 100 MΩ, at +20 °C (500 V DC)
Pt1000, DIN EN 60751, class B (Perfect Sensor Protection with IP68) Sensor external
multi-range switching with 8 switchable measuring ranges
see table (other ranges optional)
T
above +100 °C, operating range –50...+150 °C
max
with manual zero point correction (± 10 K)
typically ± 0.2 K at +25 °C
0 - 10 V or 4... 20 mA
2-wire connection
cable gland, stainless steel V2A (1.4305)
(M 20 x 1.5; with strain relief, exchangeable, inner diameter 6 - 12 mm) or
M12 connector (male, 5-pin, A-code) according to DIN EN 61076-2-101
stainless steel V4A (1.4571),
with non-distortion cover bolting,
impact-resistant, high EMI shielding,
corrosion, temperature, weather- and UV-resistant
143 x 97 x 61 mm (Tyr 2E)
Silicone, SiHF, 2 x 0,25 mm²; cable length (KL) = 1.5m
(other lengths and jacket materials,
e.g. PTFE or glass fibre with steel mesh,
available on request)
pipe feeder, made of stainless steel V4A (1.4571), Ø = 6 mm, L = 50 mm
0.14 - 1.5 mm², via screw terminals
endless strap with metal tightener (included in the scope of delivery)
Ø = 13 - 92 mm (¼ - 3"), L = 300 mm
measuring transducer –30...+70 °C
< 95 % r. H., non-precipitating air
III (according to EN 60 730)
IP 65 (according to EN 60 529) Housing tested,
TÜV SÜD, Report No. 713160960B (Skadi2)
IP 65 (according to EN 60 529) sleeve humidity-tight (standard)
IP 68 (according to EN 60 529) sleeve water-tight (optional)
CE conformity, electromagnetic compatibility according to EN 61326, according to EMC Directive 2014 ⁄ 30 ⁄ EU
Sensor
Output
with cable gland
Pt1000
4...20 mA
Pt1000
0 -10 V
with M12 connector
Pt1000
4...20 mA
Pt1000
0 -10 V
Cable connection with M12 connector (male, 5-pin, A-code)
other measuring ranges optional
Protection type IP 68 (Sensor sleeve watertight compound-filled)
2-wire connecting leads, per running meter (silicone / PTFE / glass fibre)
Special accessories for M12 connector
®
ALTM 2 - VA with eight switchable measuring ranges, external
Type
Remote sensor
Remote sensor
Remote sensor
Remote sensor
Rev. 2022 - V14
= Q
Item No.
2001- 2151- 2200-001
2001- 2151- 1200- 001
2001- 2151-2100- 001
2001- 2151-1100- 001
on request