PARA-
DESCRIPTION
METER
NO.
Hysteresis Δt, is the operating
A1
window on each side of the set
temperature "SV"
Calibrate the measured temper-
A2
ature "PV" of the external sensor.
Corrected value is displayed.
Choose cooling or heating appli-
A3
cation
Number of external sensors con-
A4
nected
Temperature max. limit, the set
A5
temperature "SV" can not be higher
than this
Temperature min. limit, the set
A6
temperature "SV" can not be lower
than this
Alarm function, disable completely
A7
or disable buzzer
Alarm activation point, how many
°C is the measured temperature
A8
"PV" allowed to differ from the set
temperature "SV"
Operating mode, choose between
"Auto" mode with time events or
A9
"Manual" mode according to a
single set temperature "SV"
Week type, choose same program
for all 7 days, 6 days and 1 week-
A10
end day or 5 days and 2 weekend
days
Safe mode, this function will op-
erate the output of the thermostat
A11
with 50/50 duty cycle in case of
error "E1" or "E2"
AA
Set all settings back to default
VALUES
0,5°..2,5°C
-9°..9°C
00 = cooling
01= heating
01=single sensor
02 = dual sensor
15°..70°C
1°..10°C
00 = disable alarm
01 = only display
02 = display & buzzer
1°..10°C
00 = manual mode
01 = auto mode
00 = 5/2 days
01 = 6/1 days
02 = 7 days
00 = disabled
01 = enabled
05 = set to default
7
DEFAULT
SETTING
1°C
0
01
01
35°C
3°C
01
5°C
00
02
01
00