3.3 Mode Setting
In Unlock mode, Press "
select "MODE" and set a mode, and Press "
submenu (mode setting). As shown below: three modes available.
12/04/2019 MON 10:35A
TWS
7 C
COOL
Cycle: Cooling-->Heating-->DHW-->Cooling. Skip the mode cycle when there is no corresponding
mode. The DHW mode is divided into single pump (no need to select the address) and multiple pumps
(need to select address 00-15, and the address of the unit without DHW function is directly skipped).
Only Tws/T5s and address can be set in cooling heating and DHW mode. Tw/T5 can only be
displayed but not be set. DHW can only be power on/off under the MODE setting.
HP-Cooling setting range lower limit is subject to the low water outlet control setting under SERVICE
MENU. CO/FC-Cooling setting range lower limit is subject to the lowest outlet water temperature set
by antifreeze ratio under PROJECT MENU.
Note When the setting temperature is lower than 5 , the water-side system must increase
more than 15% of antifreeze, otherwise there will be a risk of damage to the unit.
Press "
" to save the settings after setting and back to homepage. Or press"
there is no operation for continuous 60s, it will save the settings and back to homepage.
" button to enter the menu setting interface, Press "▼" and "▲" buttons to
12/04/2019 MON 10:35A
9 C
TW
HEAT
" button as shown in the above figure to access the
40 C
TWS
TW
55 C
7
12/04/2019 MON 10:35A
T5S
T5
60 C
DHW
" to back. When
V.1
40 C