Addresses below can be used as 03(Read Holding Registers),
06(Write Single Register)
Data Content
FORCED HEAT2
ON
DHW SWITCH
DHW MODE
ON/OFF
Water Set T
emperature of the
selected unit
Note: 1. 06 Write register, if the value is written beyond the scope of the
note, the exception code is returned.
2. Unit Address stands for machine address 0-15, 0 stands for host 0.
Enable/Disable
202+( Unit
1/0(Available for multiple pump
Address)*100
Set as 1 is invalid before HEAT2
ENABLE is set as YES.
Enable/Disable
206+( Unit
Address)*100 1/0(Available for multiple pump
Enable/Disable
207+( Unit
Set as 1 is invalid before DHW SWITCH
Address)*100
is set as YES.
1/0(Available for multiple pump
(30 ~60 )
217+( Unit
(Available for multiple pump
Address)*100
47