Cooling Unit
IMPORTANT :
The figures shown in the table are for information purpose only. They should be checked and selected
*
to comply with the local/national codes of regulations. This is also subject to the type of
installation and conductors used.
**
The appropriate voltage range should be checked with label data on the unit.
*** Outdoor coil sensor connection is applicable for WM09/15J and 5WM10/15J cooling unit.
Cooling Unit (single phase)
Indoor Unit
*** Outdoor coil sensor connection wire
Terminal Block
(8m long) attached in the indoor unit
COMP
N1
N
L
!
Heat Pump Unit (single phase)
Indoor Unit
Outdoor coil sensor connection wire
Terminal Block
(8m long) attached in the indoor unit
4WV
OF
COMP
N1
N
L
!
All wires must be firmly connected.
All wires must not touch the refrigerant piping, compressor or any moving parts of the fan motor.
The connecting wires between the indoor unit and the outdoor unit must be clamped on the wire clamps.
The power supply cord must be equivalent to H05RN-F (245IEC57) which is the minimum requirement.
1 IM-WMJ-1207(2)_EN
10
All manuals and user guides at all-guides.com
ELECTRICAL WIRING CONNECTION
Outdoor Unit
Terminal Block
COMP
N
Power Supply Cable
There must be a double pole switch
with a minimum 3mm contact gap and
fuse/circuit breaker as recommended
in the fixed installation circuit.
Outdoor Unit
Terminal Block
4WV
OF
COMP
N
Power Supply Cable
There must be a double pole switch
with a minimum 3mm contact gap and
fuse/circuit breaker as recommended in
the fixed installation circuit.
1-10
Model
(5)WM09/10/15J
(5)SL09/10/15C
Voltage range**
Power supply cable size*
mm
2
Number of wire
2
Interconnection cable size* mm
Number of wire
Recommended fuse
A
Model
(5)WM09/10/15JR WM20/25JR
(5)SL09/10/15CR
Voltage range**
2
Power supply cable size*
mm
Number of wire
2
Interconnection cable size* mm
Number of wire
Recommended fuse
A
11/20/09, 4:32 PM
WM20/25J
SL20/25C
!
220V-240V/1Ph/50Hz +
1.5
2.5
3
3
1.5
2.5
3
3
15
20
SL20/25CR
!
220V-240V/1Ph/50Hz +
1.5
2.5
3
3
1.5
2.5
3
3
15
20