Alkalinity (CaCO3)
250 ppm max
Pressure
1.5 bar
Water spray option includes:
> Copper pipes with water duct (sprayer)
> Brass ducts (quantity will be confirmed at the order)
> Water devices:
- Manometer
- Solenoid valve
- filter
- Pressure switch
- Ambient temperature sensor
- Adjustment hand valve.
> An ambient thermostat:
You have to install a drain valve at lowest point of the installation (manual operation to be done prior winter with opened solenoid valve )
Way of control method: When all the fans of the heat exchanger are in operation and ambient temperature is over the ambient thermostat
set point, Water spray system is engaged.