Shading  incidence  need  to  be  avoided  during  PV  system  operation. 
The  system  is  not  supposed  to  be  energized  until  the  mounting 
scaffolding, fences or railing have been removed from the roof. 
Systems should be disconnected in any cases of maintenance which 
can  cause  shading  (e.g.  chimney  sweeping,  any  roof  maintenance, 
antenna/dish installations, etc). 
6.0 Maintenance  
Maxeon  recommends  visual  inspection  on  a  regular  basis  of  all 
modules  for  safe  electrical  connections,  sound  mechanical 
connection, and free from corrosion. This visual inspection should be 
performed  by  trained  personnel.  The  standard  frequency  is  once  a 
year  according  to  environmental  conditions,  periodic  cleaning  of 
modules is recommended but is not required.  Periodic cleaning has 
resulted  in  improved  performance  levels,  especially  in  regions  with 
low levels of annual precipitation (less than 46,3cm (18,25  inches)). 
Consult  your  dealer  or  supplier  about  recommended  cleaning 
schedules for your area. 
 
Table 2: Module Frame Details 
 
Platform 
Residential 
Modules 
FOR COMMERCIAL (SILVER FRAME) MODULES ONLY, INCLUDES STACKING PINS 
96 CELL COMMERCIAL MODULE 
4X Ø 4.8 mm
Drain Holes
12X Ø 6.6 mm
Mounting Holes
6X Ø 4.2 mm
Commercial 
Ground Holes
Modules
 
4X Ø 6.10 mm
Stackings Pins
398 mm
3.2 mm
Measurement Tolerances are +/‐3 mm for the Length and Width of the Module. 
© December 2021 Maxeon Solar Technologies, Ltd. All rights reserved. Specifications included in this manual are subject to change without notice. 
Module mounting and ground hole detail 
RESIDENTIAL G3 FRAME ONLY 
96 CELL MODULE FRAME DETAIL 
(Front View)
(Back View)
Method 1:
Frame Hole
Locations
 
46 mm
Safety and Installation Instructions ‐ Document 001‐15497 Rev.W
To clean a module, wash with  potable, non‐heated, water.  Normal 
water pressure is more than adequate, but pressurized water up to 
100  bar  (min.50  cm  distance)  may  be  used.  Maxeon  recommends 
using  a  large  hosepipe  and  not  to  perform  cleaning  at  high  outside 
temperatures.  Fingerprints,  stains,  or  accumulations  of  dirt  on  the 
front surface may be removed as follows: first rinse off area and let 
soak for a short period of time (5 mins). Re‐wet and use a soft sponge 
or seamless cloth to wipe glass surface in a circular motion.  
 
Fingerprints typically can be removed with a soft cloth or sponge and 
water  after  wetting.  Do  not  use  harsh  cleaning  materials  such  as 
scouring  powder,  steel  wool,  scrapers,  blades,  or  other  sharp 
instruments  to  clean  the  glass  surface  of  the  module.  Use  of  such 
materials or cleaning without consultation will invalidate the product 
warranty. As dry cleaning is also risky for Anti‐Reflective (AR) coated 
module  surface,  spinning  brush  is  not  recommended  for  module 
cleaning. 
 
 
 
 
 
128 CELL COMMERCIAL MODULE 
1046 mm
4X Ø4.8 mm
1002 mm
Drain Holes
4X Ø4.2 mm
Ground Holes
20X Ø6.8 mm
Mounting Holes
300 mm
(Back View)
4X Ø6.10 mm
Stacking Pins
398 mm
(Front View)
3,2 mm
46 mm
MAXEON SOLAR TECHNOLOGIES, LTD. 
Frame Profile 
SIDE FRAME PROFILE 
10.30 mm
46.08 mm
18.50 mm
32 mm
END FRAME PROFILE 
10.50 mm
Method 1:
Frame Hole
46.08 mm
Locations
22 mm
SIDE FRAME PROFILE 
10.30 mm
3.18 mm
46.08 mm
32 mm
With Stacking Pins 
END FRAME PROFILE
10.50 mm
46.08 mm
 
22 mm
2.20 mm
 
1.27 mm
 
18.50 mm
2.20 mm
 
 
1.27 mm
 