Symptom
• The display shows E2 and the unit
goes off automatically, with the
display continuing to show error
E2 until the anomaly is repaired.
To remove from the display, press
the On/Off key once on the control
panel or remote control.
• The display shows E3 and the unit
goes off automatically, with the
display continuing to show error
E3 until the anomaly is repaired.
To remove E3 from the display,
press the On/Off key once on the
control panel or remote control.
• When the unit starts up or runs,
the unit gives out a beeping
sound and the display shows E6
(anti-freeze sensor failure). The
unit
disconnects
although the display will show error
E6 until the anomaly is repaired.
To remove E6 from the display,
press the On/Off key once on the
control panel or remote control.
All manuals and user guides at all-guides.com
automatically,
• Centrifugal blower or condenser fan
blocked, in short-circuit or disconnected.
• 5A fuse of the centrifugal blower or 7.5A
fuse of the condenser fan blown.
• Compressor defective or failed.
• Compressor module disconnected from
the compressor or defective.
• Poor connection in anti-freeze sensor
cables or terminals.
• Anti-freeze sensor disconnected or faulty.
20
Cause
®