2.4.
Supply voltage
The EDS 601 switches on automatically as soon as sufficient supply voltage is
available. If, however, the supply voltage afterwards falls so low that reliable
operation can no longer be guaranteed, "- - - -" appears in the display and the
relays and the analogue output are switched off. As soon as sufficient voltage is
once more available the unit operates again automatically. If the voltage sinks so
low that operation is no longer possible at all, the unit switches itself off
completely.
2.5.
Dimensions
72
SP1
Prog
72
Pin connections
2.6.
PE
1
2
3
Voltage supply
Plug to DIN 43650 / IEC 4400
Pin 1: +U
B
Pin 2: 0V
Pin 3: analogue output
2.7.
Connection examples analogue output
1
EDS 601
3
2
Current output:
max. load resistance 400 Ω
164
98,7
83,5
67
SP2
G1/4"
+U
B
24 V
Signal
R
L
0 V
Voltage output:
min. load resistance 2 kΩ
PE
1
2
3
6
5
4
Relay outputs
plug to DIN 43651
Pin 1: relay 1 N/C contact
Pin 2: relay 1 N/O contact
Pin 3: relay 1 common supply
Pin 4: relay 2 N/C contact
Pin 5: relay 2 N/O contact
Pin 6: relay 2 common supply
1
+U
24 V
B
EDS 601
3
Signal
V
2
0 V
E
100,5
19