Storage & Service - Tripp-Lite SmartPro INT 450 Manuel De L'utilisateur

450-1500 va onduleur intelligent ligne interactive (230v)
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

External Battery Connector (Select Models Only)
Use to connect additional Tripp Lite battery packs for additional
runtime. Refer to the label next to the connector for the appro-
priate Tripp Lite battery pack to connect. Refer to instructions
available with the battery pack for complete connection informa-
tion and safety warnings.
Battery Replacement Door
Under normal conditions, the original battery in your UPS will last
several years. Battery replacement should be performed only by
qualified service personnel. Refer to "Battery Warnings" in the
Safety section on page 2.
Storage & Service
Storage
Turn your UPS OFF: first engage the ON/Standby Switch and release it to place
your UPS in the "Standby" mode, then disconnect the UPS power cord from the
wall outlet. If you plan on storing your UPS for an extended period of time,
recharge the UPS batteries once every three months. Follow steps #1 and #3
in the Quick Installation section and allow the UPS to charge from 4 to 6 hours.
If you leave your UPS batteries discharged for an extended period of time, they
will suffer permanent loss of capacity.
Service
If returning your UPS for service, contact your local Tripp Lite dealer or
distributor. They will refer you to a service center. Please carefully pack the UPS
using the ORIGINAL PACKING MATERIAL that came with the unit. Enclose a
letter describing the symptoms of the problem. If the UPS is within the 2 year
warranty period, enclose a copy of your sales receipt.
Specifications
Output Capacity (VA/Watts):
Battery Runtime (Half Load/
Full Load) Minutes:
Battery Recharge Time:
Approvals:
Output Capacity (VA/Watts):
Battery Runtime (Half Load/
Full Load) Minutes:
Battery Recharge Time:
Approvals:
Input Voltage (230V); Input Frequency (50/60 Hz, Auto-Selecting); On-Line Input Voltage Range (151-274 volts); Voltage-Regulated Output
Voltage Range (230V +6%/-15%); On-Battery Output Voltage Range (230V ± 5%); Output Waveform Line Mode (filtered sinewave); Output
Waveform Battery Mode (PWM sine wave); AC Surge Suppression (exceeds IEEE 587 Cat. A & B standards);
AC Noise Attenuation (>40 dB); AC TVSS Protection Modes (H to N, H to G, N to G).
The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change.
6
Smart INT 450
450/280
19/5
2-4 hrs.
UL, CE
Smart INT 1500
1500/940
25/10
2-4 hrs.
UL, CE
Smart INT 700
700/425
20/6
2-4 hrs.
UL, CE
Smart INT 1000
1000/680
23/8
2-4 hrs.
UL, CE