Storage And Service; Specifications - Tripp-Lite SmartOnline SU1000RTXL2U Guide De L'utilisateur

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Storage and Service

Storage
First turn your UPS OFF: press the "OFF" switch to turn power off at the UPS outlets, then
disconnect the power cord from the wall outlet. Next, disconnect all equipment to avoid battery
drain. If you plan on storing your UPS for an extended period of time, fully recharge the UPS
batteries once every three months by plugging the UPS into a live AC outlet and letting the
UPS charge for 4-6 hours. If you leave your UPS batteries discharged for an extended period
of time, they may suffer permanent loss of capacity.
Service
If returning your UPS to Tripp Lite, please carefully pack the UPS using the ORIGINAL
PACKING MATERIAL that came with the unit. Enclose a letter describing the symptoms of the
problem. If the UPS is within the 2 year warranty period, enclose a copy of your sales receipt.

Specifications

All Models: Input Frequency (50/60 Hz Auto-Selecting); Output Waveform in Line and Battery Modes (Pure Sine Wave);
Transfer Time: (0 ns.); Maximum Harmonic Distortion with Linear Load (< 3%); Maximum Harmonic Distortion with
Nonlinear Load (< 6%); Battery Recharge Time to 80% Capacity (2-4 hours).
Model
Input Voltage (< 70% Load):
Input Voltage (Full Load):
Output Voltage:
Input Breaker Rating:
Input Plug Type:
Recommended Utility Amps:
Output Capacity (VA/Watts):
Battery Runtime (Half Load/Full Load) Min.:
System Battery Voltage:
Approvals:
Model:
Input Voltage (< 70% Load):
Input Voltage (Full Load):
Output Voltage:
Input Breaker Rating:
Input Plug Type:
Recommended Utility Amps:
Output Capacity (VA/Watts):
Battery Runtime (Half Load/Full Load) Min.:
System Battery Voltage:
Approvals:
Model
Input Voltage (< 70% Load):
Input Voltage (Full Load):
Output Voltage:
Input Breaker Rating:
Input Plug Type:
Recommended Utility Amps:
Output Capacity (VA/Watts):
Battery Runtime (Half Load/Full Load) Min.:
System Battery Voltage:
Approvals:
All manuals and user guides at all-guides.com
SU1000RTXL2U
65-138V
80-138V
120V
15A
5-15P
15A
1000/800
18/6
36 VDC
UL, cUL, FCC, NOM
SU1500RTXL2U
65-138V
80-138V
120V
20A
5-15P
20 A
1500/1200
17/5
48 VDC
UL, cUL, FCC, NOM
SU2200RTXL2U
65-138V
80-138V
120V
30A
5-20P
20A
2200/1600
18/6
48 VDC
UL, cUL, FCC, NOM
14
SU1000RTXL2UHV
SUINT1000RTXL2U
130-275V
130-275V
160-275V
160-275V
208V
230V
8A
8A
6-15P
IEC 320-C14
15A
10A
1000/800
1000/800
18/6
18/6
36 VDC
36 VDC
UL, cUL, FCC, NOM
CE
SU1500RTXL2UHV
SUINT1500RTXL2U
130-275V
130-275V
160-275V
160-275V
208V
230V
10A
10A
6-20P
IEC 320-C14
15 A
15 A
1500/1200
1500/1200
17/5
17/5
48 VDC
48 VDC
UL,cUL, FCC, NOM
CE
SU2200RTXL2UHV
SUINT2200RTXL2U
130-275V
130-275V
160-275V
160-275V
208V
230V
15A
15A
6-20P
IEC 320-C20
20A
20A
2200/1600
2200/1600
18/6
18/6
48 VDC
48 VDC
UL, cUL, FCC, NOM
CE

Publicité

Table des Matières
loading

Table des Matières