The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall
be flushed with OFN to render the unit safe. This process may need to be repeated several
times. Compressed air or oxygen shall not be used for this task.
Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to
fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down
to a vacuum. This process shall be repeated until no refrigerant is within the system. When the
final OFN charge is used, the system shall be vented down to atmospheric pressure to enable
work to take place. This operation is absolutely vital if brazing operations on the pipe-work are
to take place.
Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is
ventilation available.
13.Charging procedures
In addition to conventional charging procedures, the following requirements shall be followe d.
Ensure that contamination of different refrigerants does not occur when using charg ing
equipment. Hoses or lines shall be as short as possible to minimise the amount of refrigerant
contained in them .
Cylinders shall be kept uprigh t.
Ensure that the refrigeration system is earthed prior to charging the system with refrigera nt.
Label the system when charging is complete (if not alread y).
Extreme care shall be taken not to overfill the refrigeration system .
Prior to recharging the system it shall be pressure tested with OFN. The system shall be lea k
tested on completion of charging but prior to commissioning. A follow up leak test shall b e
carried out prior to leaving the site.
14.Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar wit h
the equipment and all its detail. It is recommended good practice that all refrigerants are
recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be tak en
in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electric al
power is available before the task is commence d.
a) B ecome familiar with the equipment and its operatio n.
b) I solate system electrically .
c) B efore attempting the procedure ensure that:
Me chanical handling equipment is available, if required, for handling refrigerant cylinder s;
A ll personal protective equipment is available and being used correc tly;
Th e recovery process is supervised at all times by a competent perso n;
Re covery equipment and cylinders conform to the appropriate standar ds.
d) P ump down refrigerant system, if possible .
e) I f a vacuum is not possible, make a manifold so that refrigerant can be removed from vario us
parts of the system .
f) M ake sure that cylinder is situated on the scales before recovery takes place .
g) S tart the recovery machine and operate in accordance with manufacturer's instructions .
h) D o not overfill cylinders. (No more than 80 % volume liquid charge) .
i) D o not exceed the maximum working pressure of the cylinder, even temporarily .
j) W hen the cylinders have been filled correctly and the process completed, make sure that t he
cylinders a nd