6. VENTING

The Power Vent is suitable for through-the-wall venting,
and for connection to vent pipes and breaching smaller
than the standard flue for the same atmospheric
appliance.
WARNING: No substitutions of flue pipe or vent
A
cap material are allowed. Such substitutions would
jeopardize the safety and health of inhabitants.
CAT III FLUE PIPE
BY OTHERS
Figure 25. Through-the-Wall (Sidewall) Venting
DIVERTER
(FIXED)
MOTOR
30
12" MIN
(305 mm)
D-15 VENT
TERMINATION
Figure 27. Induced Draft Vent Testing, Typical Models 0514–1826
JACKET TOP
Figure 26. Vent Pipe Transition, Models 0514-1223
Termination
The through-the-wall vent cap MUST be mounted on
the exterior of the building. The vent cap cannot be
installed in a well or below grade. The vent cap must
be installed at least 1 ft above ground level and above
normal snow levels. The Raypak-approved stainless
steel through-the-wall vent cap must be used (sales
order option D-15).
BAROMETRIC DRAFT
CONTROL
BOILER DRAFT
MEASURING
POINT A
8" X 7"
TRANSITION
COUNTERWEIGHT
IS DRAWN TIGHT
AND FIXED FOR
OPERATION IN
CANADA