Environment; Unpacking - Tripp-Lite AG-054D Serie Manuel Du Propriétaire

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3. General Information

3.3 Environment

Maximum Operating Temperature
• Inside rack: up to 100°F (37°C)
• Outside rack: up to 95°F (35°C)*
* Cooling performance will be reduced if the outside rack temperature reaches 95~113°F (35 ~ 45°C).
If the outside rack temperature is greater than 113°F (45°C), the system will go into protection mode (standby).
Performance-Rated Conditions
• Inside rack: 64.0-98.6°F (17.7~37°C), 20%~80%
• Outside rack: 55.4-95°F (13~35°C)
Minimum/maximum air temperature cooling mode test conducted at:
• Min: inside rack 55°F (12.8°C), outside rack 46.4°F (8°C)
• Max: inside rack 116.6°F (47°C), outside rack 113°F (45 °C)

3.4 Unpacking

Use care when unpacking the unit. The unit should be placed on its pallet as close to the final installation location as possible
to minimize having to move the unit at a later time.