Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5. Operation

5.3 Settings

The default password for User 1 is: 4321
Setting
Temp Setting
Humidity Setting
High Temp Alarm Band
High Humid Alarm
Band
Restart Delay Time
Control Mode: Supply
Air (Default)
Enable Maintenance
Description
The desired temperature of the discharge air.
The target relative humidity of the dehumidification
system.
If the discharge temperature goes below this value, an
alarm is triggered.
If the return air humidity exceeds the humidity setting
+ the high humid band setting, an alarm is triggered.
For example, if the user humidity setting is 50% and
the user wants the high humidity alarm to trigger
at 80% RH, set this to 30%. If dehumidification
mode is enabled, a high-humidity alarm will engage
dehumidification mode.
Restart delay after restoring power. If power is lost,
the cooler will automatically restart after this delay
time.
The cooling control strategy will be based off
the temperature of the discharge air. Return air:
The cooling control strategy will be based off the
temperature of the entering air.
Allows the ability to engage Maintenance Mode from
the homepage.
Notes
If setting the control mode to Return Air,
this setting becomes "Return Air Temp."
The cooler cannot add humidity to the air.
If setting Control Mode to Return Air, you
MUST ADJUST this setting to be based off
of the return air temperature instead.
If the load is lower than 30% of rated
cooling capacity, which may cause
frequent cooler on/off cycling, it is
recommended to set Control Mode to
"Return Air." Otherwise, set Control Mode
to "Supply Air."
This allows Maintenance Mode to be
engaged from the homepage without a
password.
17

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Srcool3ktp

Table des Matières