Product Description
Temperature controller for heating applications with additional
alarm relay for rail mounting. Will be delivered with a 3-wire Pt100
temperature sensor.
Functional Description
If the actual temperature (P01) falls below the control setpoint
(P02 minus hysteresis P03), the control relays switches the heating
pipeline ON. The integrated alarm relay (SPDT contact) allows to
forward error messages with occuring undertemperature, sensor
break or short circuit. While probe malfunctions, the control relay
switches continuously on or off, depending on configuration.
Operation
Easy setpoint setting while the actual temperature is displayed:
• Press „⇑" or „⇓" Display shows current setpoint and flashes
• Set new setpoint by „⇑/⇓"
• Wait 3 seconds
New value will be stored, display jump back to the actual temperature.
All selectable parameters hold a parameter number (e.g. P03),
see next page.
Calling up Parameters
• „P"
Par.No. appears
• „⇑/⇓" Select Par.No.
• „P"
Value visible
• „⇑/⇓" Change value
• „P"
New value is stored, back to Par.No.
Auto scrolling
Hold '⇑/⇓' -keys to scroll values automatically.
Parameter Lock
If you want to protect parameters P03...P07 against operation by
mistake, do the following:
• Press "P"
• Select P09 by ⇑/⇓
• Press "P" once more
• Select CodeNo. (11) by ⇑
• Press "P" again, Par.No. appears
• Then set P08 to "1" Now P03...P07 cannot be changed.
If you don´t press any key for about one minute, the access code is
canceled.
Error Messages
With an occuring error, the display shows an error code after
a 5 sec. delay.
Error Codes
E01 Sensor short circuit or temperature <=-19,5°C
E02 Sensor broken or temperature >=99,5°C
E03 Sensor 3rd wire broken or R >= 7,8 Ohm
E04 Temperature Low Alarm
Check of device type
Hold key „P" for more than 2 sec., then type (C11) and software version
(r03) will be displayed.
Set Device to Default Settings
• Set P09 to „-07"
• Press „P" as long as first „C11" and then „deF" is displayed.
Now the device is resetted.
Parameter Explanation
P01
Actual sensor temp. °C (disp.only)
P02
Control Setpoint Affects to relay 1, range P04...P05, [5°C]
P03
Switching hysteresis of P02 range 1..5K [1K]
P04
Highest adjustable Control Setpoint Range 0...+63°C [+10°C]
P05
Lowest adjustable Control Setpoint Range 0°C...P04. [2°C]
P06
Fail Safe mode
0 = Relay OFF at probe fault
[1] = Relay ON at probe fault
P07
Low Temp. Alarm Threshold –15...(P02-P03)°C, [0°C] Can be
de-activated: Set value to –15, press „⇓", display shows „oFF"
*P08
Parameter Lock
[0] = Parameter P03...P07 unlocked
1 = Parameter P03...P07 locked
P09 Access Code to unlock P08 (11).
Values in brackets [..] are factory set.
* Code necessary for operation.
Technical Data
Supply Voltage
Power consumption
Relay Rating at 250V~
Relay K1
Relay K2
Temp. Range working
Storage
Display Range
Resolution
Accuracy
Display
Relay position indicator
Screw terminals
Ingress Protection
TC RU C-BE.БЛ08.B.01433
Installation
Precautions!
•
Electrical installation and putting into service must be done from
authorized personnel.
•
Please note the local safety instructions!
•
Please note the maximum ratings !
If you have to lengthen the sensor cables, use a shielded type with one
end of the shield connected to a ground terminal near the controller.
Don't install the cable in parallel to mains voltage wires. The sum of the
wire restance may not increase 7,5 Ohms. After the power has been
switched on, the controller will display the actual sensor temperature.
Please Note Safety Instructions!
Please read this manual carefully before using the product. The
guarantee will lapse in case of damage caused by failure to comply
with these operating instructions! This documentation was compiled
with utmost care, however, we cannot guarantee for its correctnesss
in every respect.
230V AC, 50-60 Hz
max. 5 VA
16A res., 6A ind., 80A
(20ms) (Type RT33K, Schrack)
8A res., 3A ind.
–10...+55°C
–20...+60°C
–19,5...+99,5°C
0,5 K
± 1K, ± 2 Digits (0..50°C)
LED red 1/2"
1,2 mm red
2,5 mm²
IP 30 (Terminals: IP 20 )