ADEUNIS LoRaWAN MODBUS MASTER Guide Utilisateur page 37

Masquer les pouces Voir aussi pour LoRaWAN MODBUS MASTER:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

LoRaWAN MODBUS MASTER - Guide utilisateur / User guide version V2.0.0
There will be as many alarm frames transmitted as VALUE s read on the slave registers exceeding the configured thresholds.
The settings associated with this mode of operation are:
Acquisition period (register S320)
Supply time of the external load (slave) before the Modbus request (register 322)
Alarms configuration (registers S350, 355, 360, 365, 370, 375, 380, 385, 390, 395).
High threshold alarms (registers S351, 356, 361, 366, 371, 376, 381, 386, 391, 396).
Hysteresis of high threshold alarms (registers S352, 357, 362, 367, 372, 377, 382, 387, 392, 397).
Low threshold alarms (registers S353, 358, 363, 368, 373, 378, 383, 388, 393, 398).
Hysteresis of low threshold alarms (registers S354, 359, 364, 369, 374, 379, 384, 389, 394, 399).
The complete list of registers can be found in paragraph 3.4.
E.g.:
Register
VALUE encoding
S320
Decimal
S322
Decimal
S350
Hexadecimal
S351
Hexadecimal
S352
Hexadecimal
S353
Hexadecimal
S354
Hexadecimal
IMPORTANT : alarms and thresholds are set to a maximum of 4 bytes (ie 2 maximum Modbus registers).
For a value defined on one register, the user can choose the data type between unsigned or signed 16-bit integer. For a value defined on 2
registers, the user can choose the type of data between: unsigned 32-bit integer or signed 32-bit integer or unsigned 32-bit integer (word swap)
or signed 32-bit integer (word swap).
VALUE
Result
360
Periodic mode with a period of 360x10s = 3 600 seconds = 1hour
200
The supply time of the external load (slave) before the Modbus request is
200 x100ms= 20 000ms ie 20s
0x0A106827
Alarm 1 configuration:
Slave address = 0x0A
First register address = 0x1068
Data type : 32-bit unsigned integer (bits 4 to 6 = 2)
Modbus register type: input registers (bit 2 = 1)
Active thresholds: low and high (bits 0 to 1 = 3)
0x00124F80
High threshold of alarm 1 is 1,200,000 (decimal)
0x2710
Hysteresis of high threshold of alarm 1 is 10,000 (decimal)
0x00061A80
Low threshold of alarm 1 is 400,000 (decimal)
0x2710
Hysteresis of low threshold of alarm 1 is 10,000 (decimal)
FR
EN
Page
37
of 43

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Arf8240aa

Table des Matières