Scame electrical solutions ADVANCE-GRP 16A Installation, Utilisation Et Entretien page 18

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 24
ADVANCE-GRP[GD]
4.3 HOW TO INSTALL AUXILIARY CONTACT [EARLY MAKE - LATE BREAKE]
ADVANCE-GRP[GD] 16/32A
DELAY
The side, which controls the auxiliary contacts, that allows to have one auxiliary contact delayed, is in the marked position
(DELAYED) in the above figure. The available auxiliary contact used is normally open 'N.A.', installed on the holder marked as
DELAY. The auxiliary contacts closes the contacts after closing the contacts of the disconnector. And opens, the Auxiliary contacts,
before opening the disconnector contacts.
4.3.1 Electrical Parameters - Auxiliary Contact
The parameters relating to the safety , available only for ATEX certification, is not possible to mount auxiliary contacts for IECEx
certification. For Russian Market the auxiliary contacts must be certified EAC Ex.
4.3.1.1 Switch type ZBWE
For ADVANCE-GRP[GD] 16/32A/63A
Maximum Supply Voltage: 415 V
Maximum Current: 4 A
Maximum Dissipation: 1W
Wiring by screw clamp 2x 1,5 mm ² or 1 x 2.5 mm ² with tip.
Torque: 0,8Nm à 1,2Nm max
4.3.2 ATEX Certification – Auxiliary Contact
Type
ZBWE-....
4.3.3 IECEx Certification – Auxiliary Contact
Type
ZBWE-....
MP39683
Insertion aux. contact "B"
B
A
Insertion aux. contact "A"
V max - I max
EX-TECH SOLUTION
415V – 4A
Ex db eb IIC Gb
V max - I max
EX-TECH SOLUTION
415V – 4A
Ex db eb IIC Gb
ADVANCE-GRP[GD] 63A
DELAY
Mode of
ATEX Certificate
protection
INERIS 02 ATEX 9007U
Mode of
IECEx Certificate
protection
IECEx INE 13.0063U
18
Insertion aux. contact "B"
B
A
Insertion aux. contact "A"
Ambient
Temperature
-50°C / +75°C
Ambient
Temperature
-50°C / +75°C
ZP90904-6