ADVANCE-GRP[GD]
Example Marking Label ATEX / IECEx.
5 0 4 . 1 6 8 3
2 0 2 2
INERIS 15ATEX0017X
IECEx INE 15.0033X
Ex db eb IIC T5 Gb
Ex tb IIIC T80°C Db
IP66
Tamb. -35°C to +60°C
WARNING: DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT
Example Marking Label EAC Ex.
5 0 4 . x x x x . RU
2 0 1 8
НАНИО ЦСВЗ
N° TC RU C-IT.AA87.B.00XXX
1Ex d e IIC T5 Gb X Ta -50°C to +60°C
1Ex d e IIC T6 Gb X Ta -50°C to +50°C
Ex tb IIIC T80°C Db X IP66
ПРЕДУПРЕЖДЕНИЕ: НЕ ОТКРЫВАТЬ ПРИ ВОЗМОЖНОМ ПРИСУТСТВИИ ВЗРЫВООПАСНОЙ СРЕДЫ
THIS DOCUMENT SHOULD BE READ CAREFULLY BEFORE INSTALLATION
1. INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR SAFE USE
1.1 SAFETY RULES
ADVANCE-GRP[GD] are designed as Group II Category 2 equipment and is suitable for use for fixed installation in areas with
explosion hazard designated Zone 1/21 and Zone 2/22.
These operating instructions must be kept in safe place for later consultation. Use ADVANCE-GRP[GD] only for their intended
duty in the undamaged and clean condition, and only where the resistance of the material to the surroundings is assured. No
modifications are allowed to the ADVANCE-GRP[GD] that are not expressly mentioned in this instruction manual.
When installing the ADVANCE-GRP[GD] the clearance and creepage distance shall be duly considered as topic 5.3 table 8.
The ADVANCE-GRP[GD] are available in materials GRP with the following rated current 16A, 32A, 63A, 125A. For all version
available the handle is lockable in position 0 and 1. The plug can be to pull-out only when the handle is in position 0 (zero).
1.2 CONFORMITY TO STANDARDS
The socket ADVANCE-GRP[GD] are designed for Zone 1/21 and Zone 2/22 according to :
• EN IEC 60079-0:2018
• EN 60079-1:2014
• EN IEC 60079-7:2015+A1:2018
• EN 60079-31:2014
• EN 60309-1:1999+A1:2007+A2:2012
• EN 60309-2:1999+A1:2007+A2:2012
• EN 60309-4:2007+A1:2012
• IEC 60079-0:2017
• IEC 60079-1:2014
• IEC 60079-7:2017
• IEC 60079-31:2013
• IEC 60309-1:1999+A1:2005+A2:2012
• IEC 60309-2:1999+A1:2005+A2:2012
• IEC 60309-4:2006+A1:2012
• ГОСТ 31610.0-2014(IEC 60079-0:2011)
MP39683
2P+ 16A
6h 200-250V~
0051
II 2GD
2P+ 16A
6h 200-250V~
14
WARNING
Tcable 80°C when the
maximum Ta is +60°C
BHИМАНИЕ
Teмnepaтypa кaбeля 80°C,
когда максимум
Ta составляет +60°C
ZP90904-6