Operation
Transmitter set-up is done using the Configuration set. This is available
as an accessory (see page 6). The following table shows the structure of
the PC- Configuration software ReadWin
ration:
Presettable parameters
Standard settings
• Sensor type
• Connection mode (2-, 3- or 4-wire connec-
tion)
• Units (°C/°F)
• Measurement range start (depends on sensor)
• Measurement range end (depends on sensor)
Expanded
• Cold junction compensation (internal/exter-
nal on TC-connection)
settings
• Compensation resistance (0 to 20
on 2-wire connection
• Fault condition reaction (
≥
21.0 mA; > 21.5 mA is guaranteed)
• Output (analogue standard/inverse)
• Damping (0 to 8 s)
• Offset (-9.9 to +9.9 K)
• Measurement point identification/TAG
Service functions
• Simulation (on/off)
®
For detailed ReadWin
2000 operating instructions please read the on-
line documentation contained in the ReadWin
®
2000 interactive menu ope-
Ω)
≤
3.6 mA or
®
2000 software.
=
Exploitation
La configuration du transmetteur est réalisée à l'aide du kit de configu-
ration, disponible comme accessoire (voir page 6).
Le tableau suivant montre la structure de la configuration par menu du
®
logiciel PC ReadWin
2000. :
Paramètres réglables
Réglages
• Type de capteur
• Type de raccordement (2-, 3- ou 4-fils)
standard
• Unité de mesure (°C/°F)
• Début d'échelle (en fonction du capteur)
• Fin d'échelle (en fonction du capteur)
Autres réglages
• Point de référence (interne/externe
raccordement thermocouple)
• Compensation résistance de ligne (0 à 20
raccordement 2-fils
• Comportement en cas de défaut
≤
(
3,6 mA or
> 21,5 mA est garanti
• Sortie (analogique standard/inverse)
• Temps d'intégration (0 à 8 s)
• Offset (-9,9 à +9,9 K)
• Désignation du point de mesure / TAG
Fonction
• Simulation (on/off)
maintenance
Des informations détaillées sur la commande via ReadWin
figurent dans la documentation en ligne du logiciel.
≥
21,0 mA;
®
2000
Ω)
5