Operating conditions

The stated outputs of the units are obtained under the reference conditions outlined in ISO 8528-1(2005):
Total barometric pressure: 100 kPa - Ambient air temperature: 25°C (298 K) - Relative humidity: 30%.
The unit's output is reduced by approximately 4% for every additional 10°C and/or approximately 1% for every additional 100m in
altitude. Units can only operate while stationary.
8.2
Capacity of the generating set
Before connecting and operating the unit, calculate the electrical power required by the units to be used (in watts)*. To ensure
optimal operation, the total wattage of all equipment used at the same time must be:
-
greater than 60% of the rated load for the unit (risk of insufficient load);
-
less than the rated load for the unit during continuous operation (risk of overload).
If the unit is run under or over its rated load frequently or for long periods of time, it can start to wear very quickly. Damage caused
in this way will not be covered by the warranty.
*
This load is usually indicated in the technical specifications or on the manufacturer's plate for the equipment. Some equipment requires a higher
load when starting. This minimum required power must not exceed the unit's maximum power
1136_EN.docx
Check that:
The checks before starting have been
performed.
YES
The start-up procedure has been
followed correctly.
YES
The equipment to be used has not
been connected prior to starting.
YES
The spark plug is in good condition and
correctly connected.
YES
The oil level is correct.
YES
The fuel level is correct.
YES
The air filter is in good condition.
YES
Maintenance has been correctly
performed on the unit components.
YES
Have the unit checked by one of our
agents*.
The circuit breaker(s) has/have been
tripped.
YES
The connected equipment and their
power cords are not faulty.
YES
Have the unit checked by one of our
agents*.
20/122
Section 7. Repairing minor faults
Solutions to be applied:
Perform the necessary checks.
NO
Re-read the start-up procedure and repeat
the start-up attempt.
NO
Disconnect the equipment then try to start
NO
the unit again.
Replace the spark plug (330540567).
NO
Top up with oil.
NO
Fill up with fuel.
NO
Clean the air filter.
NO
Perform maintenance on the unit as per
NO
the recommendations.
Check the capacity of the unit and press
the circuit breakers.
NO
Try with another item of equipment and
NO
another power cord.
*France: 0.806.800.107 (call charge).