6.2

Assembly and installation

 Observe the
Safety
 Observe nationally applicable installation regulations for all work.
 Observe the
Special application conditions
Installation requirements:
 Install the devices in compliance with the current editions of the relevant parts of EN 60079 or equiva-
lent IEC specifications.
EN 60079-10-1 Potentially explosive atmospheres - Part 10-1:
Classification of areas subject to gas explosion
EN 60079-10-2 Potentially explosive atmospheres - Part 10-2:
Classification of areas subject to flammable dust
EN 60079-14
Potentially explosive atmospheres - Part 14:
Project planning, selection and installation of electrical systems
Minimum requirements for cable glands:
Ex-e cable gland for a permissible temperature range from -20°C ... +85°C, equipped with an O-ring and pro-
tection type IP 66/67. A long connection thread is necessary >12mm.
Cable glands of the following types have been tested to ensure that the housing is vapor-proof under continu-
ous use:
Hummel HSK-K-Ex-Active, M20x1,5, EC type-examination certificate BVS 14 ATEX E 025 X:
– Sealing range 7 – 12 mm,
– Sealing range 10 – 14 mm,
The sealing screw can be replaced by the cable glands specified above.
Note for the selection of the connection cable:
The temperature of 70°C is not exceeded at the cable inlet point.
 Protect connection cables against pulling and twisting.
03/2021
Quadro LED-RGB-3G/3D Operating Instructions
information!
Hummel type No.: 1.292.2016.31 (factory assembled and tested)
Hummel type No.: 1.292.2016.30