ENGLISH
Single Entry Power Connection with Junction Box Installation Instructions
APPROVALS
Hazardous Locations
(2)
Class I, Div. 2, Groups A, B, C, D
(1)
®
Class II, Div. 2, Groups E, F, G
Class III
CLI, ZN1, AEx e II T*
(3)
(JBS-100-A only*) Ex eb IIC T* Gb
IECEx
JBS-100-A is IECEx certified for use with:
BTV-CR/BTV-CT:
QTVR-CT:
XTV-CT:
KTV-CT:
HTV-CT:
VPL-CT:
(4)
Class I Division 2 (Zone 2**), Groups A, B, C, D
Class I Zone 2 IIC
Ex eb IIC T* Gb; Class I Zone 1 AEx eb IIC T*Gb
Ex tb IIIC T*°C Db; Zone 21 AEx tb IIIC T*°C Db
*
For system Temperature Code, see heating cable or design documentation
Except VPL, HTV (FM approval only)
(1)
Except HTV
(2)
(3)
Except KTV-CT
(4)
For HTV-CT only ** Per CE Code Table 18
KIT CONTENTS
Item
Qty
Description
A
1
Stand assembly
B
1
Core sealer
C
1
Green/yellow tube
D
1
Cable lubricant
E
1
Cable tie
F
1
Lid
G
1
Box with terminal blocks
2 | nVent.com/RAYCHEM
(1)
(3)
IECEx BAS 20.0011X
IECEx BAS 20.0013X
IECEx BAS 20.0012X
IECEx BAS 20.0014X
IECEx PTB 21.0007X
IECEx BAS 20.0008X
DESCRIPTION
The nVent RAYCHEM JBS-100-A and nVent RAYCHEM JBS-100-A6 are NEMA
4X-rated power connection kit. It is designed for use with nVent RAYCHEM
BTV-CR, BTV-CT, QTVR-CT, XTV-CT, KTV-CT, HTV-CT and VPL-CT industrial
parallel heating cables.
The JBS-100-A6 utilizes larger terminal blocks to accommodate up to 6 AWG
power wires.
This kit may be installed at temperatures as low as –67°F (–55°C). For easier
installation store above freezing until just before installation.
For technical support call nVent (800) 545-6258.
TOOLS REQUIRED
• Wire cutters
• Utility knife
• Large slotted screwdriver
• Wire stripper (for VPL-CT)
• 1/4 in or smaller flat-blade screwdriver
ADDITIONAL MATERIALS REQUIRED
• Pipe strap
OPTIONAL MATERIALS
• Recommended conduit drain:
JB-DRAIN-PLUG-3/4IN P/N 278621-000
• Small pipe adapter for 1 in (25 mm) and smaller pipes:
Catalog number JBS-SPA P/N E90515-000
A
B
C
D
• Adjustable pliers
• Needle nose pliers
• Marker
• GT-66 or GS-54 glass cloth tape
G
F
E