Tripp-Lite PDU3XMV6G32 Manuel De L'utilisateur page 12

Unités de distribution de l'énergie 0u triphasées munies d'instruments de mesure
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Features
C13
C19
Bank Status LED
Push-to-Reset Guard
21-03-407-93338E.indb 12
21-03-407-93338E.indb 12
Outlets: During normal operation, the outlets distribute AC power to
connected equipment.
Bank Status LED: Once the unit is powered on, each Bank Status LED
will illuminate when the associated bank is ready to distribute live AC
power.
LED Color
Bank Status
Green
On
Yellow
On
Red
Off
Red Flashing
Off
Off
Off
Note: Colors noted here reflect standard LED configuration. See chart on page 9 for
full LED color definitions.
Circuit Breaker: Each Load Bank is protected by a circuit breaker. If the
connected equipment load exceeds the Maximum Load Rating for those
banks of the PDU, the circuit breaker will trip. Disconnect excess load and
reset the breaker.
Note: Each breaker comes equipped with a push-to-reset guard to prevent
accidental breaker tripping. To turn off the breaker, insert a flathead screwdriver into
the reset slot.
Mounting Brackets: Use these brackets as an alternate PDU mounting
method.
Mounting Buttons: Come pre-installed on the back side of the PDU and
are used for toolless mounting.
Note: Four additional mounting buttons are included for alternate rack styles.
PDUMVROTATEBRKT Mounting Accessory: Use these V-shaped
brackets to mount the PDU with its outlets facing the rear of the rack.
12
Comments/Notes
Normal operation.
Bank's current has exceeded 80% of its current
rating.
Bank's voltage is below the Low Voltage
threshold.
Circuit breaker for this bank has tripped.
Bank is powered off.