Group Address Allocation Lower Group (bi-level KNX Address Room):
Before the values are transmitted, there must be defined values saved in Sequence 8.
This is the case for default settings at the time of delivery (255 for all channels).
To reset the default settings use either the defined value with DPT 5.001 (group address x/0-511) or the func-
tion „Central On" (group address x/1552) all values to 255.
Then save this to Sequence 8 (group address x/1551).
This establishes a maximum value for every channel.
Dimming Channel:
Addresses 1024 - 1535
Table 1:
Possible Dimming Value as 4 bit Object:
0 =
Stop
1 =
100% down
2 =
50% down
3 =
25% down
4 =
12% down
5 =
6% down
6 =
3% down
7 =
1% down
8 =
Stop
9 =
100% up
10 =
50% up
11 =
25% up
12 =
12% up
13 =
6% up
14 =
3% su
15 =
1% up
Using the automatic dimming function affects the performance when a dimming telgram is received.
Choose Sequence:
Addresses 1536 - 1543
A complete sequence with 512 channels can be output via the DMX bus.
All previously saved values are displayed on channels 1-512.
There is a choice of 8 sequences at the addresses 1536-1543.
The default value at the time of delivery is 255 for sequence 8 and 0 for sequences 1-7.
Save Sequence:
Addresses 1544-1551
Here the current DMX values can be saved in one of the 8 sequences.
The current brightness will be saved. There is a choice of 8 sequences at the addresses 1544-1551.
Central On:
Address: 1552
All 512 channels display 100% when a 1 is transmitted and 0% when a 0 is transmitted.
Dimmer Repetition Rate:
Address: 1553
Set repetition rate parameters
The repetition rate affects the dimming time.
At increments of 1%, a dimming time of 1.5 sec * is achieved.
Standard settings can be set using S3 (1 .. 15 (F) ).
20
with DPT 3.007: 4 bit Value (Dimming)
with DPT 1.001 1 bit Value (Switching)
with DPT 1.001 1 bit Value (Switching)
with DPT 1.001 1 bit Value (Switching)
with DPT 5.001 1 byte Value ( 0 .. 250 )