General Description - Gewiss Chorus GW90871 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 26

3 GENERAL DESCRIPTION

The KNX-DMX Gateway is an Interface between the KNX bus and the DMX512 bus.
It combines elements of building automation with a multitude of lighting and special effects devices for every
need.
The KNX-DMX Gateway is unidirectional, receives data telegrams on the KNX bus and transmits the data
onto the DMX512 bus.
The interface allows the DMX512 actuators to communicate via the KNX bus using the full
range of the channel.
The KNX-DMX Gateway contains 8 adjustable sequence positions within the whole channel range.
Individual scenes with all 512 channels can be saved and retrieved using KNX group addresses.
This function allows all channels to be connected simultaneously to one single object without causing any
undo load on the KNX bus.
The sequences are saved internally and can be retrieved even after a power outage.
(A sequence can only be saved 10000 times during the lifetime of the device.
The automatic save function should not be set for short intervals.)
The set value in sequence 8 is also „on" for all channels when using 1bit objects.
The KNX-DMX Gateway is ready to use and can be positioned to the main group addresses with an S1rotary
switch.
It is not necessary to project via the ETS.
1. Clamp DC IN (9...30V)
2. Clamp KNX BUS
3. Clamp DMX/RS485
4. USB Connector
5. RS-232 Connector
6. Rotary switch Main Group ETS
7. Push button programming KNX Physical address
8. Rotary switch for Function Soft Start
9. Rotary switch for Function Dimming
10.
Reset