6.APPENDIX
(2) Cable specification
1.
Single phase unit
Nameplate
maximum
Phase line
current
No more
2¡Á 1.5mm
than 10A
2¡Á 2.5mm
10~16A
16 ~25A
2¡Á 4mm
25 ~32A
2¡Á 6mm
32 ~40A
2¡Á 10mm
40 ~63A
2¡Á 16mm
63~75A
2¡Á 25mm
75~101A
2¡Á 25mm
101~123A
2¡Á 35mm
123~148A
2¡Á 50mm
148~186A
2¡Á 70mm
186~224A
2¡Á 95mm
2. Three
phase unit
Nameplate
maximum
Phase line
current
No more
3¡Á 1.5mm
than 10A
10~16A
3¡Á 2.5mm
16 ~25A
3¡Á 4mm
25 ~32A
3¡Á 6mm
32 ~40A
3¡Á 10mm
40 ~63A
¡Á 16mm
3
63~75A
¡Á 25mm
3
75~101A
3¡Á 25mm
101~123A
3¡Á 35mm
123~148A
3¡Á 50mm
148~186A
3¡Á 70mm
186~224A
3¡Á 95mm
When the unit will be installed at outdoor, please use the cable which can against UV.
Earth line
MCB
2
2
1.5mm
20A
2
2
2.5mm
32A
2
2
4mm
40A
2
40A
2
6 mm
2
63A
10mm
2
2
80A
16mm
2
2
100A
mm
25
2
2
125A
mm
25
2
2
160A
35mm
2
2
50mm
225A
2
2
70mm
250A
2
2
95mm
280A
2
Earth line
MCB
2
2
1.5mm
20A
2
2
32A
2.5mm
2
40A
2
4mm
2
40A
6 mm
2
2
63A
10mm
2
2
80A
16mm
2
2
100A
mm
25
2
2
125A
mm
25
2
2
160A
35mm
2
2
50mm
225A
2
2
70mm
250A
2
2
95mm
280A
2
19
Creepage protector
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
Creepage protector
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
Signal line
2
¡Á
n 0.5mm
Signal line
2
¡Á
n 0.5mm