LERBAKKEN 10, 8410 RØNDE DENMARK
9113Ax Installation:
Non Hazardous area or Zone 2
Supply: 19.2 – 31.2 VDC
(terminal 31,32)
(terminal 91,92,93,94,95)
Input
CH1 (terminal 41,42,43,44)
CH2 (terminal 51,52,53,54)
Status Relay. terminal (33,34)
Voltage max:
Power max:
Current max:
For installation in Zone 2, the module shall be installed in an enclosure in type of protection Ex n or
Ex e, providing a degree of protection of at least IP54. Cable entry devices and blanking elements
shall fulfill the same requirements.
For installation on Power Rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit
type 9410 (Type Examination Certificate IECEx KEM 08.0025X) is allowed.
For Installation in Zone 2 the following must be observed.
The 4501 programming module is to be used solely with PRelectronics modules. It is important that
the module is undamaged and has not been altered or modified in any way. Only 4501 modules
free of dust and moisture shall be installed.
Revision date:
2016-04-07
28
-20 ≤ Ta ≤ 60ºC
44
43
42
41
54
53
52
51
91 92 93 94 95
Power
Rail
125 VAC / 110 VDC
62,5 VA / 32 W
0.5 A AC / 0.3 ADC
Version Revision:
V5 R0
9113 - Version de produit 9113-004
4501
34
33
32
31
14
13
12
11
9113
Output:
(terminal 11,12,13,14)
Zone 2 Installation
32 VAC / 32 VDC
16V A / 32 W
0.5 A AC / 1 ADC
Prepared by:
PB
9113QI01
Page:
4/4