For safe installation of 9113 the following must be observed. The module shall only be
installed by by qualified personnel who are familiar with the national and international laws,
directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
For Installation in Zone 2 the following must be observed.
The 4501 programming module is to be used solely with PR electronics modules. It is important
that the module is undamaged and has not been altered or modified in any way. Only 4501
modules free of dust and moisture shall be installed.
IECEx Certificate:
Marking 9113Bx:
Marking 9113Ax
Standards:
Supply terminal (31,32)
Voltage :
Status Relay. terminal (33,34)
Voltage max:
Power max:
Current max:
Installation notes:
Install in pollution degree 2, overvoltage category II as defined in IEC60664-1.
Do not separate connectors when energized and an explosive gas mixture is present.
Do not mount or remove modules from the Power Rail when an explosive gas mixture is present.
Disconnect power before servicing.
The wiring of unused terminals is not allowed.
In type of protection [Ex ia Da] the parameters for intrinsic safety for gas group IIB are applicable.
For installation in Zone 2, the module shall be installed in an enclosure in type of protection Ex n or
Ex e, providing a degree of protection of at least IP54. Cable entry devices and blanking elements
shall fulfill the same requirements.
For installation on Power Rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit
type 9410 (Type Examination Certificate IECEx KEM 08.0025X) is allowed.
Revision date:
2016-04-07

IECEx Installation drawing

KEM 09.0052 X
[Ex ia Ga] IIC/IIB/IIA
Ex nA nC IIC T4 Gc
[Ex ia Da] IIIC
[Ex ia Ma] I
II 3 G Ex nA nC IIC T4 Gc
IEC60079-0:2011, IEC60079-11:2011, IEC60079-15:2010
19.2 – 31.2 VDC
125 VAC / 110 VDC
62,5 VA / 32 W
0.5 A AC / 0.3 ADC
Version Revision:
V5 R0
9113 - Version de produit 9113-004
9113QI01
Zone 2 Installation
32 VAC / 32 VDC
16 VA / 32 W
0.5 A AC / 1 ADC
Prepared by:
PB
Page:
1/4