Télécharger Imprimer la page

Bradley S19-921 Guide D'installation page 6

Lavador de ojos on-site de alimentación por gravedad

Publicité

Les langues disponibles

Les langues disponibles

S19-921
Maintenance
Follow the manufacturer's instructions for the proper use of water preservative.
Inspect eyewash unit
1 . Visually inspect the eyewash unit weekly for cleanliness and proper solution level (per ANSI Standard
Z358 .1-2009) .
2 . Activate the eyewash unit each time the solution is replaced to ensure proper operation . If the unit is not
working properly, remove it from the hazard area and contact Bradley Corporation immediately .
• Check the sprayheads' water spray pattern for an even, continuous flow . The sprayheads are attached
to the arm with screws and can be detached from the tray for cleaning or obstruction removal, if
necessary, and reattached (use a ⁹⁄₆₄" hex-head Allen wrench to remove and reinstall the sprayheads) .
• Check the water supply hose at the basin of the eyewash unit for cracks, leaks or wear .
• Check the entire unit for possible water leakage .
• Check the solution for contamination and replace with fresh solution, if necessary .
Clean eyewash unit
When using potable water and water preservative (recommended):
1 . Carefully remove the eyewash tank from the pedestal and drain the water solution from the tank (dispose
of the solution properly) . For ease of draining, the pedestal has a drain hole which will accept a ½" I .D .
tube at the underside of the hole (tube supplied by others) (see page 5 for drain hole location) .
2 . Clean the inside of the tank using warm water and a mild soap product; rinse thoroughly .
3 . Refill the eyewash tank following the procedures outlined in Step 2 found on page 4 . Follow instructions
of the preservative manufacturer for the proper use of water preservative .
4 . Reinstall the eyewash tank following the procedure outlined in Step 2 found on page 4 .
When using potable water only:
1 . Empty the tank any time from once per week to once per month, depending on the quality of your water
supply . The manufacturer is not responsible for variations in the water supply .
2 . Clean the inside of the tank using warm water and mild soap . Rinse the tank thoroughly with warm water .
3 . Refill the eyewash tank with tepid potable water .
To operate eyewash unit
1 . Begin operation by pulling down the tray .
2 . Hold eyelids open with thumbs and forefingers . Rotate eyes back and forth to ensure a complete rinse .
Allow water to bathe both eyes simultaneously for a minimum of 15 minutes .
3 . Seek medical attention immediately after use .
Do not lean on the eyewash tray when in the opened position. Damage
to unit may result.
6
11/21/2016
Bradley • 215-1546 Rev. P; ECN 16-05-066
Installation

Publicité

loading

Ce manuel est également adapté pour:

On-site s19-921