ABB ACS880-01 Mode D'emploi page 8

Masquer les pouces Voir aussi pour ACS880-01:
Table des Matières

Publicité

8 EN – USA quick installation guide
Drive type
U
= 230 V
N
ACS880-01-046A-2
ACS880-01-061A-2
ACS880-01-075A-2
ACS880-01-087A-2
U
= 460V
N
ACS880-01-040A-5
ACS880-01-052A-5
ACS880-01-065A-5
DA
ACS880-01-077A-5
U
= 525 V
USA
N
ACS880-01-07A3-7
DA
ACS880-01-09A8-7
ACS880-01-14A2-7
DE
ACS880-01-018A-7
ACS880-01-022A-7
ES
ACS880-01-026A-7
ACS880-01-035A-7
FI
ACS880-01-042A-7
ACS880-01-049A-7
FR
Install the drive on the wall
IT
See figures
A
NL
drive as shown.
PT
Check the insulation of the input and motor cables and the
motor
RU
Check the insulation of the input cable according to local regulations before
SV
connecting it to the drive.
Check the insulation of the motor cable and motor when the cable is disconnected
TR
from the drive, see figure
each phase conductor and the Protective Earth conductor using a measuring voltage
CN
of 1000 V DC. The insulation resistance of an ABB motor must exceed 100 Mohm
(reference value at 25 °C or 77 °F). For the insulation resistance of other motors,
please consult the manufacturer's instructions. Note: Moisture inside the motor
casing will reduce the insulation resistance. If moisture is suspected, dry the motor
and repeat the measurement.
Air flow
(ft
and
B
on page 81. For UL Type 12 drives: Install also the hood to the
D
on page 86. Measure the insulation resistance between
Losses
3
/min)
(W)
79
500
165
630
165
680
165
730
79
667
165
907
165
1117
165
1120
165
217
165
284
165
399
165
490
165
578
165
660
165
864
165
998
165
1120
Fuse (one per phase)
Type
JJS-80
JJS-100
JJS-125
JJS-125
JJS-60
JJS-80
JJS-90
JJS-110
JJS-15
JJS-20
JJS-30
JJS-40
JJS-50
JJS-50
JJS-60
JJS-80
JJS-80