Caution :
This device must be installed by a suitably
qualified electrician according to the
installation's standards.
Product description and operation
principles
Occupancy sensors TCC520 are presence
detectors designed to detect low amplitude
movements (movements from body or arms).
Detection is by means of a pyro-electric sensor
located under detection lens.
The occupancy sensor measures the
brightness in the room on a continuous basis
and compares it to the level preset on the
potentiometer (or by means of the remote
control EE807) or ETS parameter.
These products are part of the tebis installation
system.
Configuration
• S-mode ETS : Application software
STCC520. Database and description
available from manufacturer.
Physical addressing
2
Set potentiometer
to "Adr." position, the
red LED switches on. To exit this state, move
the potentiometer to another value.
Features
• One direct lighting control channel (relay
output of the product).
• One lighting control channel on the KNX/EIB
bus.
• Control of presence/ absence mode.
• Time and brightness adjustment via ETS or
remote control EE807.
• Area linking : the occupancy sensor in a room
can switch the light on in the corridor beside
or the opposite.
Settings
The Lux threshold and time out period can be
set with the potentiometers, by using the
installer IR remote control (EE807) or via ETS.
Action
Settings
Use Auto settings
Auto Settings
(factory) or
Put the Lux potentiometer on "auto test".
set by the remote
The settings are predefined :
control or via ETS to
Lux = 400,
switch the light
time = 20min,
automatically for a
: test mode for 2min.
defined time.
Remote control settings EE807
(manual settings inhibited).
Automatically switch
Installer settings
on the light for a
defined time.
Test and validate the
Test mode
detection zone.
Move the potentiometer
On this position, the remote control EE807
can be used.
KNX addressing
Move the potentiometer
remote control EE807 (long push > 5s. on the
SET key).
4
Test Mode
This mode makes it possible to validate the
detection area. To select this mode, set the
1
potentiometer
to the position "auto test".
The green or red LED behind the lens is on for
2 seconds after detection.
The red LED indicates that the light level measured
is lower than current setting.
If the green LED is on, the light level measured is
higher than current setting.
There is a time out during 2 minutes which is
reactivated after each detection.
The output (local relay and remote KNX load) is
switched during 2s. after each detection.
It is also possible to use the remote control EE807
to set the detector in test mode.
Functional modes
The detector has 2 different modes.
- Presence detection (automatic).
- Absence detection (semi-automatic)
The power up and cell operation can be set for
each mode.
A KNX pushbutton linked to the product makes it
possible to reverse the lighting output state.
This state is maintained for the time period set by
2
the potentiometer
or the remote control EE807.
Automatic mode (presence detection)
In this mode the light is controlled by motion in the
detection area and ambient light levels.
If presence is detected whilst the light levels are
below the required Lux level, the sensor is activated
and keeps the light on whilst there is still occu-
pancy and for the time out period afterwards.
Once the sensor has deactivated the lights, it will
require a new occupancy whilst the ambient light
levels are below the required Lux levels to activate
the lights again.
This mode can be changed via the IR remote
control EE807 (default mode is presence detection :
automatic).
Semi automatic mode (absence detection)
The sensor needs to be activated by a KNX
pushbutton or a user remote control input.
Once the sensor is activated, it will hold the lights
on whilst there is still occupancy and for the time
out period afterwards.
Once the sensor has deactivated the lights, it will
require another input from the wallswitch or the
remote control to switch the lights on.
Potentiometer
auto
test
1
on
auto
test
1
on
1 min
1 h
Adr
auto
1
test
to "auto test".
1
on
2
to "Adr." or use
1 min
1 h
Adr
Power Up
A parameter of the detector allows the choice
of state for the lighting after power up (mains
return).
During warm up phase, the green LED blinks.
In the Power up ON state the lighting will auto-
matically be energised when mains power is
initially supplied or returned to the sensor.
In the Power up OFF state the lighting will not
be energised and the sensor will not operate
during warm up period.
This parameter is modified using the installer
remote control EE807.
POWER UP state :
• ON : The light is immediately switched ON for
30s. after power up.
In case of detection, the light (in automatic
mode) remains on during the time delay;
otherwise the light is switched off.
• OFF : The detector switches to the selected
mode after warm up.
Active/passive cell
Active cell
The photocell will inhibit the output from the
sensor if the ambient light level is sufficient.
If the sensor detects occupancy whilst the
ambient light level is below the required Lux
level, the lights will be activated. However if
the ambient light level increases to a value
where it is above the required Lux level during
a certain time, the sensor will detect it and
switch off the light.
Passive cell
The photocell will inhibit the output from the
sensor if at the time of detection the ambient
light level is sufficient. In case of detection, if
the ambient light level increases, the photocell
will not turn off the light.
Factory settings
Luminosity threshold
Lighting time
lux
Mode
2
Power Up
Active cell (Luminosity Cell)
Technical features
Electrical characteristics
Supply voltage : KNX bus 30 V DC
Busline consumption : 12mA
Functional characteristics
lux
Lighting output operating time : 1min. —> 1 h
Brightness level : 5 —> 1000 Lux
2
Recommended installation height :
2,5 m —> 3,5m
Detection range : Ø 7m
(installed product height : 2.5m)
20 min
Products can be connected in parallel.
Hole size required : 60mm
Environment
auto
Operating temperature : -10 °C —> +45 °C
test
1
Storage temperature : -20 °C —> +60 °C
lux
lux
Class of insulation : II
2
2
IK 03
Index of protection : IP41
on
Fire resistance : 650°C
Standards : IEC 60669-1,
IEC 60669-2-1, EN 50428
20 min
Connection capacity :
0.5mm
0.5mm
400 lux
20 min.
Presence
OFF
ON
2
2
to 1,5mm
flexible,
2
2
to 1,5mm
rigid
6T 7384.b