BRAUKMANN FK06 DIALSET®
1
LOOSEN THE SETPOINT DIAL LOCKING SCREW.
2
UNSTRESS THE
PRESSURE SPRING
BY TURNING COUNTER-
CLOCKWISE
.
3
UNSCREW THE BONNET WITH A 1-5/8" WRENCH.
4
REMOVE CARTRIDGE USING A PLIERS AS A LEVER.
6
REASSEMBLE BONNET IN REVERSE ORDER.
Fig. 4. Replacing the FK06 cartridge.
38-00059EFS—05
1-5/8 WRENCH
WHEN REASSEMBLING,
5
ENSURE O-RINGS AND
WASHER ARE PROPERLY
INSTALLED
WASHER
(LIP UP)
O-RINGS
M36658A
Cleaning
CAUTION
Do not use any cleansers that contain solvents and/or
alcohol for cleaning the plastic parts.
If necessary, the filter bowl and the filter can be cleaned.
Frequency: every 6 month (depending on local operating
conditions)
To be carried out by an installation company. Detergents
must not be allowed to enter the environment or the
sewerage system!
1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Unscrew filter bowl
• Use double ring wrench ZR06F
5. Remove filter, clean and reinsert
6. Place O-ring onto filter bowl
7. Screw in filter bowl hand-tight (without tools)
8. Slowly open shutoff valve on inlet
9. Slowly open shutoff valve on outlet
DISPOSAL
• Dezincification resistant brass housing
• Brass connections
• High-quality synthetic material valve insert
• High-quality synthetic material spring bonnet with
adjustment knob and setting scale
• Spring steel adjustment spring
• Stainless steel fine filter
• Shock-resistant, clear transparent synthetic material filter
bowl
• Fibre-reinforced NBR diaphragm
• NBR seals
NOTE:
Observe the local requirements regarding correct
waste recycling/disposal!
4