CONNECTING GLOBRITE
EASYTOUCH
LOAD CENTER TO AN AUXILIARY RELAY
RISK OF ELECTRICAL SHOCK OR ELECTROCUTION
Always disconnect AC power to EasyTouch and IntelliTouch control system load
center at the circuit breaker before servicing, or removing the HIGH VOLTAGE FRONT
PANEL. Failure to do so could result in death or serious injury to installer, service
person, pool users, or others due to electrical shock.
1.
EasyTouch or IntelliTouch Control System Load Center: Unlatch the
enclosure door spring latch, and open the door.
2.
Discharge Electrostatic energy before removing the cover by first
touching the metal part of the enclosure.
3.
Loosen the two (2) retaining screws from the HIGH VOLTAGE FRONT
PANEL. Remove the panel from the enclosure.
4.
Run the GloBrite white light power cord to a auxiliary relay in the
EasyTouch/IntelliTouch load center.
5.
Connect the 120 Volt side of a 12 VAC transformer to the LOAD SIDE of
one of the auxiliary (AUX) relays in the load center.
6.
Connect the Neutral conductor from the 12 VAC transformer to the Neutral
bus bar in the load center.
7.
After the connection has been completed, close the control panel and
secure it with the two (2) retaining screws.
8.
Close the load center front door. Fasten the spring latch.