Parameters in the short parameter view
No.
Name/Value
20 LIMITS
2008 MAXIMUM
FREQ
0.0...500.0 Hz
21 START/STOP
2102 STOP
FUNCTION
COAST
RAMP
22 ACCEL/DECEL
2202 ACCELER
TIME 1
0.0...1800.0 s
2203 DECELER
TIME 1
0.0...1800.0 s
99 START-UP DATA Language selection. Definition of motor set-up data.
9901 LANGUAGE
Actual signals and parameters in the short view 31
Description
Drive operation limits
Defines the maximum limit for the drive output frequency.
Maximum frequency
Start and stop modes of the motor
Selects the motor stop function.
Stop by cutting off the motor power supply. The motor
coasts to stop.
Stop along a ramp. See parameter group
ACCEL/DECEL.
Acceleration and deceleration times
Defines the acceleration time 1, ie the time required for the
speed to change from zero to the speed defined by
parameter
2008 MAXIMUM
• If the speed reference increases faster than the set
acceleration rate, the motor speed will follow the
acceleration rate.
• If the speed reference increases slower than the set
acceleration rate, the motor speed will follow the
reference signal.
• If the acceleration time is set too short, the drive will
automatically prolong the acceleration in order not to
exceed the drive operating limits.
Actual acceleration time depends on parameter 2204 RAMP
SHAPE 1 setting.
Time
Defines the deceleration time 1, ie the time required for the
speed to change from the value defined by parameter
MAXIMUM FREQ
to zero.
• If the speed reference decreases slower than the set
deceleration rate, the motor speed will follow the
reference signal.
• If the reference changes faster than the set deceleration
rate, the motor speed will follow the deceleration rate.
• If the deceleration time is set too short, the drive will
automatically prolong the deceleration in order not to
exceed drive operating limits.
If a short deceleration time is needed for a high inertia
application, note that the ACS310 cannot be equipped with
a brake resistor.
Actual deceleration time depends on parameter 2204
RAMP SHAPE 1 setting.
Time
Selects the display language used on the Assistant control
panel.
Note: With the ACS-CP-D Assistant control panel, the
following languages are available: English (0), Chinese (1),
Korean (2) and Japanese (3).
22
FREQ.
Def/FbEq
E: 50.0 Hz
U: 60.0 Hz
1 = 0.1 Hz
COAST
1
2
5.0 s
1 = 0.1 s
5.0 s
2008
1 = 0.1 s
ENGLISH