INSTALLATION Continued
If a vent line from the gas appliance pressure regulator is
used, it should be installed to the outdoors in accordance
with local codes or, in the absence of local codes, with the
National Fuel code, ANSI Z223.1, Natural Gas Installation
Code, CAN/CGA-B149.1 or the Propane Installation Code,
CAN/CGA-B149.2, as applicable.
WARNING: Failure to install a pressure regulator will void the
equipment warranty!

Rigid Connections

Double-check any installer-supplied intake pipes visually
and clear any dirt particles, threading chips, or other foreign
matter before installing in a service line. Those particles will
clog orifices when gas pressure is applied.
Flexible Couplings & Connectors
If the unit is to be installed with flexible couplings and/or
quick-disconnect fittings, for an appliance equipped with
casters, the installation shall be made with a heavy duty, AGA
design-certified commercial flexible connector or at least
3/4" NPT (with suitable strain relief's) in compliance with
the Standard for Connectors for Movable Gas Appliances,
ANSI Z21.69 /CSA 6.16, and a quick-disconnect device that
complies with the Standard for Quick-Disconnect Devices
for Use With Gas Fuel, ANSI Z21.41 / CSA 6.9, and adequate
means must be provided to limit the movement of the
appliance without depending on the connector and the
quick-disconnect device or its associated piping to limit
the appliance movement and the location(s) where the
restraining means may be attached to the appliance shall be
specified.
Further, if the unit is to be installed on a non-combustible
surface that is equipped with casters, means must be
provided to limit the movement of the unit on this surface.
An addendum included with these instructions indicates the
location(s) where the restraining means may be attached to
meet the above standards.

Manual Pilot Valve

Check all gas connections for leaks using a soapy solution
before! Lighting any pilots. DO NOT USE AN OPEN FLAME
TO CHECK FOR LEAKS! Putting an open flame beside a new
connection is not only dangerous, but will often miss small
leaks that a soapy solution would find.
Page 8
All manuals and user guides at all-guides.com
All Garland appliances are adjusted and tested before
leaving the factory, effectively matching them to sea
level conditions. Adjustments and calibrations to assure
proper operation may be necessary on installation to meet
local conditions, low gas pressure, differences in altitude,
variations in gas characteristics, to correct possible problems
caused by rough handling or vibration during shipment, and
are to be performed only by qualified service personnel.
These adjustments are the responsibility of the customer,
installer and/or dealer and are not covered by the Garland
warranty.
All burners are equipped with constant-burning pilots. These
should be manually lighted immediately after the gas is
turned on and the system is checked for leaks. An adjustment
screw for each pilot is located on the gas manifold, and can
be accessed through openings in the valve panel between
the valve knobs.
WARNING: All connections must be sealed with a joint
compound suitable for LP gas, and all connections must be
tested with a soapy solution before lighting any pilots!

Initial Pilot Light

Initial pilot light is in the following sequence:
1. Turn the manual shut-off valve on the incoming service
2. Turn all burner valves "OFF".
3. Close all pilot adjusting screws (clockwise turn all the
4. Wait for any accumulated gas to disperse.
5. Open the manual shut-off valve.
6. Apply a lighted match or taper to a pilot burner and open
7. Adjust the pilot flame for the desired characteristics.
8. Turn "ON" that main burner and watch to make sure it
9. Repeat steps 6 through 8 to light all remaining pilots.
line "OFF"
way in).
that pilot's adjustment screw gradually until the pilot
lights.
lights from the pilot, then turn the burner "OFF".
Part # 9229077 (05/28/09)