SINGLE - IMPULSE BUTTON (Dip 4 on mode OFF)
to connect with terminals 8 and K of the control board (it operates these
commands: OPEN - STOP - CLOSE - STOP - .....).
PUSH-BUTTON PANELS AND SELECTORS
If 2 or more push-button panels are wired, connect the opening and
closing commando in parallel (8-9 e 8-11), and the stop contacts in series
(8-2).
Any key selector shall be connected between terminals 8-9 and 8-11.
If no stop button is requested, connect the terminals through a jumper 8-2.
RADIO TRANSMITTER
It operates the opening of the boom when this is closed. While the gate
is opening, the radio transmitter cannot give any command, until the
opening limit switch is reached.
When the boom is open, it operates its closing.
If you press the radio transmitter while the boom is closing, the barrier
inverts its movement.
F
UNCTIONING OF SAFETY ACCESSORIES
PHOTOCELLS (set at 12Vdc)
Photocells (fitted as Figures 2 and 3 show) can interrupt the movement
of the automation both when it opens and when it closes
´Dip 3 on mode ON´ (starting the movement again as the interposition is
finished).
If you command the gate to move in the event of a photocell breakdown,
the blinker will not emit its signals and the motor will not run.
If photocells are engaged when the boom is open, they reset the waiting
time again before the automatic closing is actuated (if Dip 5 is or will be
operated).
PNEUMATIC SAFETY STRIPS OR FOTOCOSTA UNITS
Connect the safety strips to terminals 8-10.
As the safety strip is operated, the movement reverses.
12VDC CONNECTION OF THE WARNING LIGHT LED
(TO SIGNAL THE AUTOMATION IS OPEN)
Connect the warning light to terminals D- and 7 (max. 6 watt).
The signal is given when the automation is open, partly open or, in any
case, not totally closed.
230V 40W BLINKER
If you want the Blinker to start three seconds before the motor does,
position ´Dip 6 on mode ON´.
T

ECHNICAL SPECIFICATIONS

Humidity
Power supply voltage
Frequency
Transient voltage drops
Motor output
Max. flasher output
Max. card absorption (excluding accessories)
Current available for terminals D+D- 0.8 A ± 15% - 12 V dc
Protection rating
Equipment weight
Overall dimensions
ELECTRONIC SAFETY DEVICES
The limit switches, the motor and the blinker of RAPID PARK are already
connected to the electronic control panel.
Only one push-button panel, the photocells and, of course, the power
voltage need to be wired.
Persons and things shall be protected against any possible crushing
caused by unwanted commands: to this purpose you must install at least
a couple of photocells or a sensor (of the pneumatic or photocell type)
under the boom, as Fig. 1-2-12 shows.
For information about the connections or technical data of accessories,
follow the relevant instruction books.
LAYOUT NORMAL FUNCTIONING
LINE
230VAC
< 95% condensate free
230 V ac ± 10%
50/60 Hz
20 ms
736 W
40 W - 250 Vac cosƒi = 1
30 mA
IP54
0.8 kg
14.7x6x18 cm
DIP4 - OFF
G G
B B
8